Goodrive100-PV Series Solar Pumping VFD Options and use
68
Model
Recommended cable size
(mm
2
)
Terminal
screw
Tightening
torque
(Nm)
(+)/(-), R/S/T, U/V/W
PE
GD100-2R2G-2-PV
2.5
2.5
M4
1.21.5
GD100-7R5G-4-PV
4
4
M5
22.5
GD100-004G-2-PV
4
4
M5
22.5
GD100-011G-4-PV
6
6
M5
22.5
GD100-5R5G-2-PV
6
6
M5
22.5
GD100-015G-4-PV
10
10
M5
22.5
GD100-7R5G-2-PV
10
10
M5
22.5
GD100-018G-4-PV
16
16
M5
22.5
GD100-022G-4-PV
25
16
M5
22.5
GD100-030G-4-PV
25
16
M6
46
GD100-037G-4-PV
35
16
M6
46
GD100-045G-4-PV
35
16
M8
10
GD100-055G-4-PV
50
25
M8
10
GD100-075G-4-PV
70
35
M8
10
GD100-090G-4-PV
95
50
M12
3140
GD100-110G-4-PV
120
70
M12
3140
GD100-132G-4-PV
185
95
M12
3140
GD100-160G-4-PV
240
95
M12
3140
GD100-185G-4-PV
120*2P
150
M12
3140
GD100-200G-4-PV
120*2P
150
M12
3140
Note:
For the cable selection for model IP54, see the cables applicable to the models with the
same power as model IP54 in this table.
It is appropriate to use the recommended cable size under 40°C and rated current. The
wiring distance should be no more than 100m.
If the control cable and power cable must cross, the angle between them must be 90°.
If the inside of the VFD is moist, the insulation resistance will decrease. If there is moisture
in the VFD, dry up the VFD and measure the humidity again.