Goodrive20-EU series VFD Function parameters
76
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
The raising time of the traverse frequency: The
time from the lowest point to the highest one.
The declining time of the traverse frequency: The
time from the highest point to the lowest one.
Setting range of P08.15: 0.0 100.0%
(relative to the set frequency)
Setting range of P08.16: 0.0 50.0%
(relative to the traverse range)
Setting range of P08.17: 0.1 3600.0s
Setting range of P08.18: 0.1 3600.0s
P08.19
Linear speed/
frequency
decimals
Ones: decimals of linear speed display
0: no decimals
1: one decimal
2.: two decimals
3: three decimals
Tens: decimals of frequency display
0: two decimals
1: one decimal
0x00
P08.20
Analog
calibration
function setting
0: Disabled
1: Enabled
0
P08.21
Deceleration
time for
emergency
stop
0.06553.5s
0.0 indicates coasting to stop.
0.0s
P08.22
Delay to enter
the sleep state
0.03600.0s
It indicates the delay to enter the sleep state, and
it is valid only when P01.19 is set to 2.
2.0s
P08.23
Preset voltage
and frequency
0: 230 V preset voltage and 50Hz preset frequency
1: 220 V preset voltage and 60Hz preset frequency
2: 400 V preset voltage and 50Hz preset frequency
3: 460 V preset voltage and 60Hz preset frequency
2
P08.24
Enabling
energy
consumption
braking stop
0: Disable
1: Enable
1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive20-EU VFD Series and is the answer not in the manual?

INVT Goodrive20-EU VFD Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive20-EU VFD Series
CategoryDC Drives
LanguageEnglish

Related product manuals