Goodrive300 Series VFD Function parameters
113
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
the
counter-electrom
otive force
constant
E’(V/1000r/min),
then:
E=E’×n
N
/100
0
3. Iif the name
plate does not
designate the
above
parameters,
then:
E=P/√3×I
In the above
formulas: n
N
is
the rated rotation
speed, P is the
rated power and I
is the rated
current.
Setting range:
010000
P12.24
Initial pole
position of
synchronous
motor 2
(reserved)
0FFFFH (reserved)
0x0000
P12.25
Identification
current of
synchronous
motor 2
(reserved)
0%50%(the rated current of the motor)
(reserved)
10%
P12.26
Motor 2
overload
protection
0: No protection
1: Common motor(with low speed compensation)
2: Variable frequency motor (without low speed
compensation)
2