Goodrive300 Series VFD Basic operation instruction
170
0
1
2
3
4
5
.
.
.
.
29
30
P06.01
P06.03
P06.04
P06.02
T delay
T delay
T delay
T delay
0
1
P06.05 Output polarity
(Default value is 0)
(Default value is 0)
(Default value is 1)
(Default value is 5)
P06.00
HDO output type
selection
0
1
0
1
0
1
Delay
0 Invalid 1 Running
3 Reverse running 4 Jogging
6 FDT1 7 FDT2
9 Zero-speed running 10 Upper-limit frequency arrival
12 Ready 13 Pre-exciting
15 Underload pre-alarm 16 Simple PLC stage completion
2 Forward running
5 VFD fault
8 Frequency arrival
11 Lower-limit frequency arrival
14 Overload pre-alarm
17 Simple PLC cycle completion
18 Set counting arrival ·19 Fixed counting arrival
21 Length arrival 22 Running time arrival
20 External fault valid
23
Modbus communication virtual
terminal output
24
POROFIBUS communication
virtual terminal output
25~30 Reserved
0
1
-1
-1
-1
-1
P17.12
P07.38
Fault?
Faul
t
Run
Y BIT0 HDO BIT1
ROI BIT2 RO2 BIT3
P06.05, P17.12, P07.38 display
P06.00
0: Open collector high-
speed pulse output
1: Open collector pole
output
P06.07
P06.09
P06.11
P06.13
Y
RO2
ROI
HDO
Digital switch-off delay time
Digital output
T delay
T delay
T delay
T delay
Delay
P06.06
P06.08
P06.10
P06.12
Digital switch-on delay time
The following table is the option of the four function parameters and selecting the repeated output
terminal function is allowed.
Set value
Function
Instructions
0
Invalid
The output terminal has no function.
1
Running
Output ON signal when the VFD is running and there
is frequency output.
2
Forward running
Output ON signal when the VFD is running forward
and there is frequency output.
3
Reverse running
Output ON signal when the VFD is running reverse
and there is frequency output.
4
Jogging
Output ON signal when the VFD is jogging and there
is frequency output.
5
VFD fault
Output ON signal when the VFD is in fault
6
FDT1
Please refer to P08.32 and P08.33 for detailed
information.
7
FDT2
Please refer to P08.34 and P08.35 for detailed
information.
8
Frequency arrival
Please refer to P08.36 for detailed information.
9
Zero-speed running
Output ON signal when the output frequency and
given frequency of the VFD is 0 at the same time.
10
Upper-limit frequency arrival
Output ON signal when the running frequency of the

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive300 Series and is the answer not in the manual?

INVT Goodrive300 Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive300 Series
CategoryDC Drives
LanguageEnglish

Related product manuals