Goodrive300 Series VFD Function parameters
53
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
power outage
the power off and then power on.
0: Ddisable
1: Enable, if the starting need is met, the VFD will
run automatically after waiting for the time defined
by P01.22.
P01.22
Waiting time of
restart after
power outage
The function determines the waiting time before
the automatic running of the VFD when powering
off and then powering on.
Output frequency
Running
Power off Power on
Running
t
t1 t2
t1=P01.22
t2=P01.23
Setting range: 0.03600.0s (valid when
P01.21=1)
1.0s
P01.23
Start delay
time
The function determines the brake release after
the running command is given, and the VFD is in
a stand-by state and wait for the delay time set by
P01.23
Setting range: 0.060.0s
0.0s
P01.24
Delay time of
the stop
speed
Setting range: 0.0100.0 s
0.0s
P01.25
0Hz output
selection
Select the output mode at 0Hz.
0: Output without voltage
1: Output with voltage
2: Output at DC braking current at stopping
0
P02 Group Motor 1
P02.00
Motor type 1
0: Asynchronous motor
1: Synchronous motor
Note: Switch the current motor by the switching
channel of P08.31.
0
P02.01
Rated power
of
asynchronous
motor 1
0.13000.0kW
Set the parameters of
the controlled AM.
In order to ensure
control performance, set
Depend
on
model