iMars grid-tied solar inverters Operation
31
5.1 Inspection before operation
The following items must be checked strictly before running the PV grid-connected inverter
(including but not limited to the following items):
(1) Ensure the installation site meet the requirement mentioned in section 4.2.2 for easy
installation, removing, operation and maintenance.
(2) Ensure the mechanical installation meet the requirement mentioned in section4.3.
(3) Ensure the electrical installation meet the requirement mentioned in section 4.4.
(4) Ensure all switches are off.
(5) Ensure the open-circuit voltage of PV module conforms to the parameter requirements
of inverter DC side in Technical parameters;
(6) Ensure all electrical safety precautions are clearly-identified on the installation site.
In order to ensure a safe, normal and stable operation of the PV power
generation system, all the newly installed, renovated and repaired PV
grid-connected power generation system and its grid-connected inverter must
undergo inspection before running.
5.2 Inverter grid-connected running
Start the inverter according to below steps to achieve grid-connected operation of the inverter:
Note
It is a must to select the country to set grid-connected standard
during the initial operation of the inverter, see details at section
6.5.
Keep the power-on state of the inverter for at least 30 minutes, and complete the
charging of built-in clock battery of the inverter to ensure the clock can run
normally!
(1) Confirm the requirements in section 5.1 are fulfilled;
(2) Close the breaker on inverter public grid AC side;
(3) Close the integrated DC switch of the inverter;
(4) Close the circuit switch on PV string DC input side;
(5) Observe the LED indicator state of the inverter and the information displayed by LCD.
Refer to chapter 5 for LED state indicator and LCD display information.