26
Program Erase – Complete Program Reset
Activating this function will erase all saved irrigation programs in the MC-E controller. However, it will not erase the
current time, date or any Option or SETUP settings.
Reset All Programs
Step 1 – Place the Function Dial to the Program Erase position.
Step 2 – Enter and press .
Press the
button to clear any “Key Entry Error”.
Press the button to exit or press to accept.
Step 3 – Return the Function dial to AUTO/RUN position to exit Program Erase.
Program Erase – Complete Controller Reset
Activating this function will erase all data settings in the MC-E controller. The rmware will revert back to factory default
settings.
Reset the Controller
Step 1 – Place the Function Dial to the Program Erase position.
Step 2 – Enter and press .
Press the
button to clear any “Key Entry Error”.
Press the button to exit or press to accept.
Step 3 – Return the Function dial to AUTO/RUN position to exit Program Erase.
Station Test
The MC-E provides the Station Test to allow you to activate all stations whether they are assigned to a program or not.
When a Station Test is performed, the controller will sequence through all the stations and activate them for the specied
duration.
Perform Station Test
Step 1 – Place the Function Dial to the Station Test position.
Step 2 Enter the station runtime from 01 second to 30 minutes (seconds must be entered with 0 rst, i.e. 45 seconds,
enter 045) and press the to initiate the test.
If no runtime is entered before pressing the button, the controller will test each station
for two minutes.
Press the
button to clear any “Key Entry Error”.
Example: Test each station by activating them for one minute. Press the buttons.
Press the button to advance to the next station.
Place the Function Dial to any position to Cancel the procedure.
Step 3 – Return the Function dial to AUTO/RUN position to exit Station Test.