Remote Operation Mode 
  Copyright ©ITECH Electronic Co., Ltd.  32 
Mode: SIGNAL (Single connection mode) 
MUX (Multiple connection mode) ADDR: Local address (0 to 30
, the 
factory default setting is 0) 
Start Bit    8 Data Bits  Parity=None  Stop Bit 
 
To set the multi-unit connection mode, access the system Menu→SYST 
SET→COMM→RS485→MODE→MUX, to turn on the chain mode. 
 
Set each unit with a different Address (0 to 30). Then by using RS485, connect 
the first power supply in the chain to a PC. Now, multiple units daisy-chained 
via RS485 can be controlled by one PC by using the commands specific for 
multi-unit connection. See “Programming Guide” section for details. 
The figure below is a schematic diagram of the connection of 4 machines.