Inspection and Installation
Copyright ©ITECH Electronic Co., Ltd. 27
AC Power Input Level
The AC input of this series is a three-phase AC power (three-phase four-wire)
by default, and the model of 3kVA and 5kVA power supply can support single
phase AC power input. The detailed specifications refer to Technical
Specifications.
Please pay attention to the AC input voltage level:
NOTE
When the AC input voltage of 5kVA and 12kVA or above are less than
240V, the output power will be derated to 60%, and when the output
exceeds the present rating, the instrument occurs protection and the
output is turned off. If a full power output is required, the AC input level
Voltage must be greater than 240V.
Connecting the Power Cord
⚫ When connecting the instrument which rated power is 3kVA or 5kVA
please take care for balanced current distribution on three phases. For single
unit, it supports single phase input, and it requires single phase or three phases
of AC distribution box (the rated AC current on L3 is 0, so, it can be connected
or not). In case multiple units are connected to the same main AC distribution
box. It is recommended to follow the suggestion connection diagram as below.
Single phase input connecting:
Multiple power supplies connect to three phase input: