14.3.2 Defective Firmware
If a wrong or corrupt firmware data was loaded or
another cause:
Delete XENAX® with DIP switch firmware recorder
and start boot loader:
DIP switch „LOAD“ ON
Logic supply ON, firmware recorder is being deleted,
wait until „F“ on display,
logic supply off,
DIP switch „LOAD“ OFF
Logic supply ON, display „F“→ boot loader active,
Ethernet connection to PC/Laptop and load new
firmware with WebMotion®.