14.3.2 Defective Firmware
If a wrong or corrupt firmware data was loaded or
another cause:
Delete XENAX® with DIP switch firmware recorder
and start boot loader:
DIP switch „LOAD“ ON
Logic supply ON, firmware recorder is being deleted,
wait until „F“ on display,
logic supply off,
DIP switch „LOAD“ OFF
Logic supply ON, display „F“ boot loader active,
Ethernet connection to PC/Laptop and load new
firmware with WebMotion®.