SECTION 2 - CONNECTING BAS TO A SERIES 100/YPAL UNIT WITH THE IPU CONTROLLER
END OF LINE TERMINATION
• While it is not always required to have End-of-
Line Termination, it is strongly recommended
• For BACnet MS/TP and N2 protocols, JCI factory
recommends using our End-Of-Line Terminator,
p/n: MS-BACEOL-0
• Other communication protocols may need to pro-
vide/install their own end-of-line terminators if
applicable
MISCELLANEOUS
• Whenever a change is made to a communication
setting, please cycle power on/off to the unit to
“lock in” the new setting
• Points list are available in section 6 of the unit
Installation, Operation, and Maintenance manual
for BACnet MS/TP, BACnet IP, MODBUS, LON,
and N2
TECHNICAL SUPPORT
• For technical support on connecting to and com-
municating with the IPU controller in the Series
100 rooftop unit, please contact Applied DX
Product Technical Support
a. 1-877-329-7430 option 2
b. applieddxtechsupport@jci.com
• For technical support with E-Links or End-of-
Line termination, please contact the Field Support
Center
a. 1-800-524-1330 options 6-1-2