EasyManuals Logo

Johnson Controls 100 Series Manual

Johnson Controls 100 Series
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #31 background imageLoading...
Page #31 background image
JOHNSON CONTROLS
31
SECTION 11 - SERIES 100: FLEXSYS OPERATION
FORM 100.50-SU8
ISSUE DATE:1/28/2016
11
Unoccupied
Unoccupied Cooling mode will be initiated by the cur-
rent zone temp being higher than the Unoccupied Zone
Cooling SP by 0.5 °F. The Night Set Back feature must
be User Enabled. Night Set Back can be found under
the Heating menu.
• Supply fan starts. Supply fan VFD is controlled to
the Active Duct Static SP
• Economizer is modulated open/closed to achieve
and maintain the MX SAT SP
AND/OR
• Compressors are cycled on/off to achieve and
maintain the MX SAT SP
• Bypass damper remains closed
• Cooling operation will continue until the current
zone temp is less than the Unocc Zone Cooling
SP by 0.5 °F
FLEXSYS: COMPRESSOR CONTROL
Occupied Cooling w/o Bypass
• S100 enters an active cooling mode.
• Unit Controller sets the “Cooling Control Offset”
to 2.0 °F.
• Unit Controller compares the current MX SAT to
the MX SAT SP ± the “Cooling Control Offset.”
• If MX SAT is > the MX SAT SP + the “Cooling
Control Offset,” the Unit Controller will:
c. Start a Compressor
OR
d. Bring on a additional stage of cooling based
on the “Next Stage to Enable”
• If MX SAT is < the MX SAT SP – the “Cooling
Control Offset,” the Unit Controller will:
• Stop a compressor based on the “Next Stage
to Disable”
Occupied Cooling w/ Bypass
• S100 unit enters an active cooling mode.
• Unit Controller sets the “Cooling Control Offset”
to 2.0 °F.
• Unit Controller compares the Evap Leaving Air
Temp to the Active Evap Leaving Air Temp SP ±
the “Cooling Control Offset.”
• If Evap Leaving Air Temp is > the Active Leaving
Air Temp SP + the “Cooling Control Offset,” the
Unit Controller will:
a. Start a compressor
OR
b. Bring On and additional stage of cooling
based on the “Next Stage to Enable”
• If the Evap Leaving Air Temp is < the Active Evap
Leaving Air Temp SP, the Unit Controller will:
• Stop a compressor based on the “Next Stage
to Disable”
FLEXSYS: HEATING
Occupied/Unoccupied heating operation will follow
the same sequence as a VAV configured unit. It is
recommended to limit the Heating SAT SP to 80.0 or
90.0 °F. This will prevent the underfloor concrete slab
from becoming too warm and then radiating heat for
an extended period of time after heating operation has
been terminated.
FLEXSYS: UNDERFLOOR TEMPERATURE
CONTROL
Dew Point Reset
This sequence changes the Active Evaporator Leaving
Air Temperature to a lower value when the temperature
of the underfloor air approaches its dew point.
• MUSThaveanunderoorslabtemperaturesen-
sor ANDanunderoorhumiditysensorinstalled.
(FieldprovidedandeldwiredtoCTB1.Canalso
be communicated from the BAS.)
• Dew Point Reset MUST be User Enabled.
• Unit controller uses the MX SAT and the
underoor humidity to calculate the underoor
dew point.
• IfUnderoorAirDewPoint≥theUnderoorSlab
Temp – 2.0 °F for 120 seconds, the unit controller
will switch from the Evap Leaving Air Temp High
SP to the Evap Leaving Air Temp Low SP.
• Unit controller will continue to use the Evap
LeavingAir Temp Low SP until the Underoor
Air Dew Point < the Underoor Slab Temp –
2.5 °F.

Table of Contents

Other manuals for Johnson Controls 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls 100 Series and is the answer not in the manual?

Johnson Controls 100 Series Specifications

General IconGeneral
BrandJohnson Controls
Model100 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals