JOHNSON CONTROLS
35
SECTION 12 - BACNET MS/TP POINTS
FORM 100.50-SU8
ISSUE DATE:1/28/2016
12
BACNET NAME
USER
INTERFACE
NAME
READ/
WRITE
BACNET/
OBJECT TYPE
AND INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
COMP_LPCO_1
SAFETY INPUT
LPCO CKT 1
STATUS
R BI09 1290
DISPLAYS THE STATUS OF THE
LOW PRESS SWITCH ON CKT 1:
0=FAULT 1=NO FAULT
COMP_LPCO_2
SAFETY INPUT
LPCO CKT 2
STATUS
R BI10 1291
DISPLAYS THE STATUS OF THE
LOW PRESS SWITCH ON CKT 2:
0=FAULT 1=NO FAULT
COMP_LPCO_3
SAFETY INPUT
LPCO CKT 3
STATUS (70-150
TON ONLY)
R BI11 1292
DISPLAYS THE STATUS OF THE
LOW PRESS SWITCH ON CKT 3:
0=FAULT 1=NO FAULT
COMP_STAT_1
SAFETY CHAIN
CKT 1 STATUS
R BI12 1293
DISPLAYS THE STATUS OF
CKT 1 SAFETY CHAIN: 0=FAULT
1=NO FAULT
COMP_STAT_2
SAFETY CHAIN
CKT 2 STATUS
R BI13 1294
DISPLAYS THE STATUS OF
CKT 2 SAFETY CHAIN: 0=FAULT
1=NO FAULT
COMP_STAT_3
SAFETY CHAIN
CKT 3 STATUS
(70-150 TON
ONLY)
R BI14 1295
DISPLAYS THE STATUS OF
CKT 3 SAFETY CHAIN: 0=FAULT
1=NO FAULT
COND_FAN_1A
COND FAN 1A/1
STATUS
R BI15 1296
DISPLAYS THE STATUS OF
COND FAN 1A/1: 0=OFF 1=ON
COND_FAN_1B
COND FAN 1B/2
STATUS
R BI16 1297
DISPLAYS THE STATUS OF
COND FAN 1B/2: 0=OFF 1=ON
COND_FAN_2A
COND FAN 2A/3
STATUS
R BI17 1298
DISPLAYS THE STATUS OF
COND FAN 2A/3: 0=OFF 1=ON
COND_FAN_2B
COND FAN 2B/4
STATUS
R BI18 1299
DISPLAYS THE STATUS OF
COND FAN 2B/4: 0=OFF 1=ON
COND_FAN_3A
COND FAN 3A/5
STATUS (70-150
TON ONLY)
R BI19 1300
DISPLAYS THE STATUS OF
COND FAN 3A/5: 0=OFF 1=ON
COND_FAN_3B
COND FAN 3B/6
STATUS (70-150
TON ONLY)
R BI20 1301
DISPLAYS THE STATUS OF
COND FAN 3B/6: 0=OFF 1=ON
COND_FAN_SPD
COND FAN
SPEED
R AI15 528
NOT USED AT THIS TIME. FOR
FUTURE USE
CONTINU_VENT
CONTINUOUS
VENTILATION
(CONSTANT
VOLUME)
R/W AV79 BV03 1104
DISPLAYS THE STATUS OF THE
CONTINUOUS VENTILATION
OPTION AND ALLOWS FOR IT
TO BE TURNED ON/OFF: 0=OFF
1=ON
DCT_ST_PR_RT
DUCT STATIC
PRESS RESET
R AI16 529
DISPLAYS THE STATUS OF THE
HARDWIRED DUCT STATIC
RESET VALUE TO CTB1 (%)
DCT_STAT_PRS
DUCT STATIC
PRESS
CURRENT (VAV
or FLEXSYS)
R AI17 530
DISPLAYS THE ACTUAL DUCT
STATIC PRESS ("WC)
TABLE 1 - BACNET MS/TP POINTS (CONT'D)