SECTION 12 - BACNET MS/TP POINTS
BACNET NAME
USER
INTERFACE
NAME
READ/
WRITE
BACNET/
OBJECT TYPE
AND INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
FURN_OUT_3
ELECT HEAT
STAGE 3 STATUS
STAGED
GAS FURN 2
LOW STATUS
MOD GAS FURN
2 LOW STATUS
R BI28 1309
DISPLAYS THE STATUS OF THE
CONTROL OUTPUT TO THE
INDICATED HEAT SECTION:
0=OFF 1=ON
FURN_OUT_4
ELECT HEAT
STAGE 4 STATUS
STAGED
GAS FURN 2
HIGH STATUS
MOD GAS FURN
2 HIGH STATUS
R BI29 1310
DISPLAYS THE STATUS OF THE
CONTROL OUTPUT TO THE
INDICATED HEAT SECTION:
0=OFF 1=ON
FURN_OUT_5
ELECT HEAT
STAGE 5 STATUS
STAGED
GAS FURN 3
LOW STATUS
MOD GAS FURN
3 LOW STATUS
R BI30 1311
DISPLAYS THE STATUS OF THE
CONTROL OUTPUT TO THE
INDICATED HEAT SECTION:
0=OFF 1=ON
FURN_OUT_6
ELECT HEAT
STAGE 6 STATUS
STAGED
GAS FURN 3
HIGH STATUS
MOD GAS FURN
3 HIGH STATUS
R BI31 1312
DISPLAYS THE STATUS OF THE
CONTROL OUTPUT TO THE
INDICATED HEAT SECTION:
0=OFF 1=ON
FURN_OUT_7
ELECT HEAT
STAGE 7 STATUS
MOD GAS FURN
1B STATUS
R BI32 1313
DISPLAYS THE STATUS OF THE
CONTROL OUTPUT TO THE
INDICATED HEAT SECTION:
0=OFF 1=ON
HEAT_ENABLE
HEATING
SYSTEM
R/W AV83 BV07 1108
A BAS COMMAND THAT ALLOWS
THE HEATING FUNCTION TO BE
TURNED ON/OFF: 0=ENABLED
1=DISABLED
HEAT_ENT_TEMP
HEAT ENTERING
TEMP
R AI22 535
DISPLAYS THE ACTUAL TEMP
OF THE AIR ENTERING THE
ELECT, STAGED GAS, OR MOD
GAS HEAT SECTIONS
HEAT_STAGES
ELECTRIC HEAT
STAGES or GAS
HEAT STAGES
R AI23 536
DISPLAYS THE NUMBER OF
ELECT OR STAGED GAS HEAT
STAGES AVAILABLE
HEAT_VACTION
HW VALVE
ACTION
R/W AV84 BV08 1109
A BAS COMMAND THAT ALLOWS
THE HOT WATER/STEAM VALVE
ACTION TO BE CHANGED:
0=DIRECT 1=REVERSE
HEATING_SAT
HEATING SUPPY
SIR TEMP
SP (VAV or
FLEXSYS)
R/W AV09 1034
DISPLAYS THE ACTIVE SUPPLY
AIR TEMP SP FOR HEATING
TABLE 1 - BACNET MS/TP POINTS (CONT'D)