SECTION 12 - BACNET MS/TP POINTS
FORM 100.50-SU8
ISSUE DATE:1/28/2016
12
BACNET NAME
USER
INTERFACE
NAME
READ/
WRITE
BACNET/
OBJECT TYPE
AND INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
OCC_MODE
OCCUPANCY
MODE STATUS
R BI35 1316
DISPLAYS THE OCC/UNOCC
STATUS WITH HARDWIRED,
COMMUNICATED, or
INTERNAL CLOCK SCHEDULE
INPUT: ENA=ENABLED/OCC
DIS=DISABLED/UNOCC
OCC_STATE
OCCUPANCY
STATE STATUS
R BI36 1317
DISPLAYS THE STATUS OF
THE HARDWIRED INPUT:
ENA=ENABLED/OCC
DIS=DISABLED/UNOCC
OCC_ZN_COOL
OCC ZONE
COOLING SP
R/W AV21 1046
DISPLAYS THE ACTIVE
OCCUPIED ZONE COOLING SP
OCC_ZN_HEAT
OCC ZONE
HEATING SP
R/W AV22 1047
DISPLAYS THE ACTIVE
OCCUPIED ZONE HEATING SP
OCCUPNCY_
CMD
OCCUPANCY
COMMAND
R/W AV88 BV12 1113
A BAS COMMAND THAT ALLOWS
THE UNIT TO BE PLACED IN THE
OCC/UNOCC MODE: 0=UNOCC
1=OCC
PRS_1_DISCH
DISCH PRESS
CKT 1
R AI31 544
DISPLAYS THE CURRENT DISCH
PRESS OF CKT 1 (PSIG)
PRS_1_SUCT
SUCT PRESS
CKT 1
R AI32 545
DISPLAYS THE CURRENT SUCT
PRESS OF CKT 1 (PSIG)
PRS_2_DISCH
DISCH PRESS
CKT 2
R AI33 546
DISPLAYS THE CURRENT DISCH
PRESS OF CKT 2 (PSIG)
PRS_2_SUCTION
SUCT PRESS
CKT 2
R AI34 547
DISPLAYS THE CURRENT SUCT
PRESS OF CKT 2 (PSIG)
PRS_3_DISCH
DISCH PRESS
CKT 3 (70-150
TON ONLY)
R AI35 548
DISPLAYS THE CURRENT DISCH
PRESS OF CKT 3 (PSIG)
PRS_3_SUCT
SUCT PRESS
CKT 3 (70-150
TON ONLY)
R AI36 549
DISPLAYS THE CURRENT SUCT
PRESS OF CKT 3 (PSIG)
PUMP_DOWN PUMP DOWN R/W AV89 BV13 1114
A BAS COMMAND THAT ALLOWS
THE PUMP DOWN FEATURE
TO BE TURNED ON/OFF: 0=ON
1=OFF
PUMP_DOWN_1
PUMP DOWN
LLSV 1 STATUS
R BI37 1318
DISPLAYS THE STATUS OF THE
OUTPUT TO THE CKT 1 LIQ LINE
SOLENOID VLV: 0=ON 1=OFF
PUMP_DOWN_2
PUMP DOWN
LLSV 2 STATUS
R BI38 1319
DISPLAYS THE STATUS OF THE
OUTPUT TO THE CKT 2 LIQ LINE
SOLENOID VLV: 0=ON 1=OFF
PUMP_DOWN_3
PUMP DOWN
LLSV 3 STATUS
(70-150 TON
ONLY)
R BI39 1320
DISPLAYS THE STATUS OF THE
OUTPUT TO THE CKT 3 LIQ LINE
SOLENOID VLV: 0=ON 1=OFF
TABLE 1 - BACNET MS/TP POINTS (CONT'D)