EasyManua.ls Logo

Johnson Controls 5 J ZE Series - Page 28

Johnson Controls 5 J ZE Series
78 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5742639-JIM-C-0220
28 Johnson Controls Ducted Systems
J05
(5.0)
208-1-60 24.4 144.2 38 4.4 7.6 10
NONE - - - 52.5 70
E05 4 1 19.2 52.5 70
E07 5.6 1 26.9 55.7 70
E10 8 1 38.5 70.1 80
E15 11.9 2 57.2 93.5 100
E20 15.9 2 76.4 117.6 125
E30 22.2 2 106.7 155.4 175
230-1-60 24.4 144.2 38 4.4 7.6 10
NONE - - - 52.5 70
E05 5.3 1 22.1 52.5 70
E07 7.5 1 31.2 61.1 70
E10 10.6 1 44.2 77.2 80
E15 15.9 2 66.2 104.8 110
E20 21.2 2 88.3 132.4 150
E30 29.6 2 123.3 176.2 200
208-3-60 16 110 24.9 4.4 7.6 10
NONE - - - 42 50
E05 4 1 11.1 42 50
E07 5.6 1 15.5 42 50
E10 8 1 22.2 49.8 50
E15 11.9 2 33 63.3 70
E20 15.9 2 44.1 77.2 80
E30 22.2 2 61.6 99 100
230-3-60 16 110 24.9 4.4 7.6 10
NONE - - - 42 50
E05 5.3 1 12.7 42 50
E07 7.5 1 18 44.6 50
E10 10.6 1 25.5 53.9 60
E15 15.9 2 38.2 69.8 70
E20 21.2 2 51 85.7 90
E30 29.6 2 71.2 111 125
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
J03 through A6ZE - With Powered Convenience Outlet (Direct Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps

Table of Contents