14. The final logging of the CK721-A controller firmware installation
actions appears in the Tera Term Pro window. Verify that you see the
same data as shown in the following figure.
When the firmware installation process is completed, the
CK721-A controller reboots and a Login prompt appears on
Tera Term Pro window.
If Tera Term Pro window does not display a Login prompt, the
firmware installation has failed (see Troubleshooting on
page 17 for more information).