Johnson Controls
5586996-JSG-A-0120 | Start-Up & Operation Guide
112
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Denitions (Units)
ERV-En MV 29787 R/W ERV-En ERV Enabled
A BAS command to enable ERW
0 = NO 1 = YES
HGR-En MV 29789 R/W HGR-En
HGRH Enabled
For Operation
A BAS command to enable HGRH
0 = none
1 = normal
2 = alternate
HGR-S MV 29791 R HGR-S HGRH Status
Displays the status of HGRH
0 = OFF/idle
1 = ON/normal command
2 = ON/alternate operation command
3 = OFF/disabled
OprSafetyCmd MV 29798 R OprSafetyCmd
Operating Safety
Command
Displays the status of safety
command
0 = normal
1 = pressurize
2 = depressurize
3 = purge
SafetyCmdSrc MV 29799 R SafetyCmdSrc
Safety Command
Source
Displays the source of safety
command input:
0 = unreliable
1 = local input
2 = network sensor
3 = high priority
Safety1 MV 29800 R Safety1
Local Safety
Command Input 1
Displays the status of local safety
command input 1 0 = false 1 = true
NetSafety MV 29801 R/W NetSafety
Network Override
Safety Command
A BAS command to override safety
command 0 = false 1 = true
SS-S MV 29802 R SS-S
Safety Switch
Status
Displays the unit safety switch status
0=normal 1=alarm
Unit-S MV 29803 R Unit-S Unit Status
Displays the unit status
0 = idle
1 = SD alarm
2 = purge command
3 = start-up wizard
ExcessOutAirFlt MV 29809 R
Not Displayed
Locally
Not Displayed
Locally
Displays the excess outside air fault
0 = normal 1 = alarm
NotEconFlt MV 29810 R
Not Displayed
Locally
Not Displayed
Locally
Displays the economizer not available
for suitable outside air conditions
0 = normal 1 = alarm
EconDampFlt MV 29811 R
Not Displayed
Locally
Not Displayed
Locally
Displays the economizer damper fault
0=normal 1=alarm
EconWhen
ShouldNotFlt
MV 29812 R
Not Displayed
Locally
Not Displayed
Locally
Displays the economizer available for
unfavorable outside air conditions fault
0 = normal 1 = alarm
MornW-En MV 29822 R/W MornW-En
Morning Warm-
Up Enabled
A BAS command to enable morning
warm-up 0 = NO 1 = YES
TempOCC MV 29825 R/W TempOCC
Temporary
Occupancy Input
A BAS command to enable
temporary occupancy input
0 = disable 1 = enable
Table 32: BACnet Points List (Continued)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls GVC Series and is the answer not in the manual?

Johnson Controls GVC Series Specifications

General IconGeneral
BrandJohnson Controls
ModelGVC Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals