Johnson Controls
5586996-JSG-A-0120 | Start-Up & Operation Guide
112
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Deîżnitions (Units)
ERV-En MV 29787 R/W ERV-En ERV Enabled
A BAS command to enable ERW
0 = NO 1 = YES
HGR-En MV 29789 R/W HGR-En
HGRH Enabled
For Operation
A BAS command to enable HGRH
0 = none
1 = normal
2 = alternate
HGR-S MV 29791 R HGR-S HGRH Status
Displays the status of HGRH
0 = OFF/idle
1 = ON/normal command
2 = ON/alternate operation command
3 = OFF/disabled
OprSafetyCmd MV 29798 R OprSafetyCmd
Operating Safety
Command
Displays the status of safety
command
0 = normal
1 = pressurize
2 = depressurize
3 = purge
SafetyCmdSrc MV 29799 R SafetyCmdSrc
Safety Command
Source
Displays the source of safety
command input:
0 = unreliable
1 = local input
2 = network sensor
3 = high priority
Safety1 MV 29800 R Safety1
Local Safety
Command Input 1
Displays the status of local safety
command input 1 0 = false 1 = true
NetSafety MV 29801 R/W NetSafety
Network Override
Safety Command
A BAS command to override safety
command 0 = false 1 = true
SS-S MV 29802 R SS-S
Safety Switch
Status
Displays the unit safety switch status
0=normal 1=alarm
Unit-S MV 29803 R Unit-S Unit Status
Displays the unit status
0 = idle
1 = SD alarm
2 = purge command
3 = start-up wizard
ExcessOutAirFlt MV 29809 R
Not Displayed
Locally
Not Displayed
Locally
Displays the excess outside air fault
0 = normal 1 = alarm
NotEconFlt MV 29810 R
Not Displayed
Locally
Not Displayed
Locally
Displays the economizer not available
for suitable outside air conditions
0 = normal 1 = alarm
EconDampFlt MV 29811 R
Not Displayed
Locally
Not Displayed
Locally
Displays the economizer damper fault
0=normal 1=alarm
EconWhen
ShouldNotFlt
MV 29812 R
Not Displayed
Locally
Not Displayed
Locally
Displays the economizer available for
unfavorable outside air conditions fault
0 = normal 1 = alarm
MornW-En MV 29822 R/W MornW-En
Morning Warm-
Up Enabled
A BAS command to enable morning
warm-up 0 = NO 1 = YES
TempOCC MV 29825 R/W TempOCC
Temporary
Occupancy Input
A BAS command to enable
temporary occupancy input
0 = disable 1 = enable
Table 32: BACnet Points List (Continued)