Johnson Controls
Start-Up & Operation Guide | 5586996-JSG-A-0120
113
Operation
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Denitions (Units)
ResetLO MV 29826 R/W ResetLO Reset Lockouts
A BAS command to reset lockouts
0 = OFF 1 = ON
HtgAdapTunEn MV 29881 R/W HtgAdapTunEn
Heating Adaptive
Tuning Enable
A BAS command to enable heating
adaptive (PID) tuning
0 = NO 1 = YES
ClgAdapTunEn MV 29882 R/W ClgAdapTunEn
Cooling Adaptive
Tuning Enable
A BAS command to enable cooling
adaptive (PID) tuning
0 = NO 1 = YES
LoadShedEnable MV 29883 R/W LoadShedEnable Load Shed Active
A BAS command to enable load shed
for automatic demand response
0 = NO 1 = YES
MornC-En MV 29891 R/W MornC-En
Morning Cool
Down Enabled
A BAS command to enable morning
cool down 0 = NO 1 = YES
OptStrt-En MV 29893 R/W OptStrt-En
Optimal Start
Enabled
A BAS command to enable optimal
start 0 = NO 1 = YES
UnitEn MV 29896 R/W UnitEn Unit Enable
A BAS command to enable/shutdown
the unit 0 = shutdown 1 = enable
HGRUnocc-En MV 29904 R/W HGRUnocc-En
HGRH Enabled
for UNOCC
Operation
A BAS command to enable HGRH
for unoccupied operation
0 = NO 1 = YES
SZVAVEn MV 29908 R/W SZVAVEn SZ VAV Enabled
A BAS command to enable SZVAV
0 = OFF 1 = ON
ADR-S MV 29910 R ADR-S
Automated
Demand
Response
Displays the automated response
status
0 = NO 1 = YES
OffDurUnocc MV 29914 R/W OffDurUnocc
OFF During
UNOCC
A BAS command to disable fan
during UNOCC mode
0 = NO 1 = YES
EconFltDetectEn MV 29915 R/W EconFltDetectEn
Economizer Fault
Detection Enabled
A BAS command to enable
economizer FDD
0 = disable 1 = enable
PIDTunRst MV 29919 R/W PIDTunRst PID Tuning Reset
A BAS command to reset PID tuning
0= false 1=true
FrAir-En MV 29933 R/W MinOA-En
Min Outside Air
Enabled
A BAS command to enable minimum
outside air damper position
0 = disable 1 = enable
EncodeType MV 29934 R/W EncodeType
BACnet Encoding
Type
A BAS command to input BACnet
encoding type
0 = ISO 10646 (UCS-2)
1 = ansi x3.4 (US-ASCII)
2 = Microsoft DBCS code page 932
(Japanese shift JIS)
3 = ISO 10646 (UTF-8)
CF-1A MV 29935 R CF-1A
Condenser Fan
1A
Displays the command of condenser
fan CF-1A 0 = OFF 1 = ON
CF-1B MV 29936 R CF-1B
Condenser Fan
1B
Displays the command of condenser
fan CF-1B 0 = OFF 1 = ON
CF-2A MV 29937 R CF-2A
Condenser Fan
2A
Displays the command of condenser
fan CF-2A 0 = OFF 1 = ON
Table 32: BACnet Points List (Continued)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls GVC Series and is the answer not in the manual?

Johnson Controls GVC Series Specifications

General IconGeneral
BrandJohnson Controls
ModelGVC Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals