BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Denitions (Units)
Humidistat MV 30063 R Humidistat Humidistat
A BAS command that allows the
control of unit by humidistat
0 = OFF 1 = ON
HtgOcc-En MV 29722 R/W HtgOcc-En
MZVAV Occupied
Heating Enabled
A BAS command that allows the user
to enable MZVAV occupied heating
mode
0 = NO 1 = YES
HtgClgSP-Mode MV 30064 R/W HtgClgSP-Mode
Heat Cool
Setpoint Mode
A BAS command that allows the user
to enable heat cool setpoint mode
0 = NO 1 = YES
Common-SP AV 30065 R/W Common-SP Common Setpoint
A BAS command to adjust common
setpoint (45.0–98.0°F)
OprEvapTempSp AV 30066 R OprEvapTempSp
Operational Evap
Temperature
Setpoint
Displays the active evaporator
temperature setpoint (°F)
OprHGRTempSp AV 30067 R OprHGRTempSp
Operational
HGRH
Temperature
Setpoint
Displays the active HGRH
temperature setpoint (°F)
DemLoadshd MV 30075 R DemLoadshd
Demand
Loadshed
Displays the demand load shed
command status 0 = NO 1 = YES
SafetySetupNI MV 30079 R/W SafetySetupNI
Safety Setup
Network Input
A BAS command to enable safety
setup
0 = Normal
1 = Pressurize
2 = Depressurize
3 = Purge
4 = Shutdown
MVCritical
ActiveEvent
0 30000 R NA NA NA
MVCritical
InactiveEvent
0 29999 R NA NA NA
MVServicePriority
ActiveEvent
0 29998 R NA NA NA
MVServicePriority
InactiveEvent
0 29997 R NA NA NA
MVService
ActiveEvent
0 29996 R NA NA NA
MVService
InactiveEvent
0 29995 R NA NA NA
NOTE: NA = Not Available
Table 32: BACnet Points List (Continued)