18 M Motor Actuators—M100C Series of Motor Actuators
M100C13
45 678
OFF
Address 20
45 6
7
8
OFF
Address 21
4
567
8
OFF
Address 22
45 6
7
8
OFF
Address 23
45 6
7
8
OFF
Address 24
45
67
8
OFF
Address 25
Figure 16: AHU Address Switch Settings
Table 7: AHU Address Switch Values
SWITCH NUMBER ON VALUE OFF VALUE
5
0—
6
04
7
02
8
01
For selection of Zone Bus, switch 5 must be ON and an additional value
of 20 added to the total of the switch settings. For example: to select L1
Address 25, set Switches 6 and 8 OFF and Switches 5 and 7 ON
(25 = 0 + 4 + 0 + 1 from the switch settings and +20 because of Zone Bus
selection). Using the switches, select any Zone address between 20 and 27
although only 20 through 25 are addressable by the AHU Controller.
The M100C is adjustable from 65 to 270 degrees of rotation.
Travel Adjustment
The controller sends position commands to the actuator ranging from
0 to 100%. The actuator responds to these commands only over its
selected range of travel.
0%
(CCW)
0%
100%
(CW)
Reverse
Action
Direct
Action
Controller Command
100%
M100C13