Input and Output wiring guidelines
I/O terminal block functions, ratings and requirements
provides information and guidelines about the functions,
ratings, and requirements for the controller input and
output terminals, and Table 4 also references guidelines
for determining proper wire sizes and cable lengths.
In addition to the wiring guidelines in I/O terminal block
functions, ratings and requirements, observe these
guidelines when wiring expansion modules inputs and
outputs:
Run all low-voltage wiring and cables separate from
high-voltage wiring.
All input and output cables, regardless of wire size or
number of wires, should consist of stranded, insulated,
and twisted copper wires.
Shielded cable is not required for input or output
cables.
Shielded cable is recommended for input and output
cables that are exposed to high electromagnetic or
radio frequency noise.
Inputs/outputs with cables less than 30 m (100 ft)
typically do not require an offset in the software setup.
Cable runs over 30 m (100 ft) may require an offset in
the input/output software setup.
M4-XPM Expansion Modules Installation Guide6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls M4-XPM and is the answer not in the manual?

Johnson Controls M4-XPM Specifications

General IconGeneral
BrandJohnson Controls
ModelM4-XPM
CategoryControl Unit
LanguageEnglish

Related product manuals