Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 13
Through addressable control modules (M510CJ), the FC-2000 can
selectively activate indicating appliance circuits or Form-C output relays
(see Figures 23 through 27).
Through the communications loop, the AIM-200 communicates with
intelligent ionization, photoelectric, and thermal detectors (Figure 28).
The capacity of each AIM-200 includes up to 99 intelligent detectors and
an additional combination of up to 99 addressable pull stations, control
modules, and monitor modules. One to ten AIM-200s can be employed,
depending on system requirements.
Notes:
1. Communications loop is supervised and power limited.
2. Maximum loop length is 10,000 feet (total twisted pair length).
3. Maximum loop voltage: 27.6 VDC.
4. Maximum loop current: 200 mA (short circuit) 100 mA (normal
operation)
5. Maximum loop resistance: 40 ohms.
6. Refer to the proper installation drawing supplied with each
communications loop appliance.