EasyManuals Logo

Johnson Controls M510CJ User Manual

Johnson Controls M510CJ
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 13
Through addressable control modules (M510CJ), the FC-2000 can
selectively activate indicating appliance circuits or Form-C output relays
(see Figures 23 through 27).
Through the communications loop, the AIM-200 communicates with
intelligent ionization, photoelectric, and thermal detectors (Figure 28).
The capacity of each AIM-200 includes up to 99 intelligent detectors and
an additional combination of up to 99 addressable pull stations, control
modules, and monitor modules. One to ten AIM-200s can be employed,
depending on system requirements.
Notes:
1. Communications loop is supervised and power limited.
2. Maximum loop length is 10,000 feet (total twisted pair length).
3. Maximum loop voltage: 27.6 VDC.
4. Maximum loop current: 200 mA (short circuit) 100 mA (normal
operation)
5. Maximum loop resistance: 40 ohms.
6. Refer to the proper installation drawing supplied with each
communications loop appliance.
Control Modules
Intelligent
Detectors
Loop Capacity

Questions and Answers: