EasyManua.ls Logo

Johnson Controls M510CJ - Operating M510 CJ Control Modules; General Alarm

Johnson Controls M510CJ
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 51
Operating M510CJ Control
Modules
Optional M510CJ control modules can be installed on the AIM-200
addressable loop. When using one or more M510CJs, four types of control
options are available: General Alarm, Control-by-Zone,
Control-by-Module, and Control-by-Detector. The M510CJ zone mapping
and address assignments required for each control option are described
below.
To set up General Alarm, set M510CJ module address in the range of
01-59 and ensure that it has not been mapped to any zones. If an alarm
occurs on the alarm bus (see Figure 6 for wiring information), the M510CJ
will be activated. This type of control can also be executed using the
manual switch on the CPU board alarm relay (manual evacuation).
Table 9: Activating M510CJs Based on an Alarm Anywhere in the
System
Alarm
From
M510CJ
Address
M510CJ Mapped
to Zone(s)?
Results
Alarm Bus 01-59 No M510CJ will be activated if not
mapped to any zone.
Alarm Bus 01-59 Yes M510CJ will not be activated if
mapped to a zone.
Alarm Bus 60-99 * M510CJ will not be activated if not
in the address range of 01-59.
* Result is the same whether M510CJ is mapped to any zone or not.
General Alarm

Related product manuals