30 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module
Figure 24: M510CJ Control Module (Form -C Relay)
To configure a M510CJ as a Form-C relay, the two tabs must be broken
off of the module. Use a pair of needle-nose pliers to break off each tab.
Connect the communications loop to M510CJ Terminals 1(-) and 2 (+).
The M510CJ occupies one module address on the loop. Set the rotary
switches on the M510CJ to the particular loop address required.
Wire the common and the normally-open or normally-closed contacts to
the M510CJ as needed.
Resistive: 2 amps @ 30 VDC
Inductive: 1 amp @ 30 VDC (0.6 pf)
0.3 amps @ 120 VDC (0.35 pf)
Contacts are not rated for pilot duty or motor loads.
Break Tabs
Communications
Loop
Connections
Contact
Connections
Contact Ratings