Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 39
Figure 34: Detector and Control Module LEDs
To program a M510CJ control module to function as an indicating
appliance circuit, press the STEP-FORWARD switch until the right-hand
display digit is blank.
Note: The function tabs on the M510CJ must not be broken for this type
of operation.
To program a M510CJ control module as a Form-C relay, press the
STEP-FORWARD switch until the right-hand display digit reads “0.” The
STEP-REVERSE switch can be used to disable the control module
(right-hand digit displays a “d”).
Accepting or Rejecting Devices
The ENTER and SKIP LEDs will flash while the AIM-200 is in
Auto-Program or Program Edit mode.
Auto-Program
To accept a new device, press the ENTER switch. To reject a device,
press the SKIP switch. In either case, the AIM-200 will advance to the
next address.
Program Edit
To store newly edited information on the device displayed, press the
ENTER switch. To leave device unchanged, press the SKIP switch. In
either case, the AIM-200 will advance to the next address.
Note: Holding in the SKIP switch will cause the AIM-200 to advance
through successive addresses quickly (10 per second).
Control Module
(IAC)
Control Module
(Form-C)
Programming
Switches