PMGB0406B rev.1
21
Models Motor FLA
1
Minimum Circuit Ampacity MOP
2
18B 1.1 1.4 15
24B 1.4 1.8 15
30B 2.3 2.9 15
36B 2.6 3.3 15
36C 2.2 2.8 15
48C/48D
2.9 3.6 15
60C/60D 4.1 5.1 15
T
able 3. Electrical Data - Cooling Only
1.
FLA = Full Load Amps.
2.
MOP = Maximum Overcurrent Protection device; must be HACR type service disconnect or time delay
fuse. Refer to local codes to determine the correct wire size.
Table 4. Electrical Heat - Minimum Fan Speed
Heater Kit
Models
1,
2, 3
Nom.
kW
@
240V
Air Handler Models
18B 24B 30B 36B 36C 48C 48D 60C 60D
6HK(0,1)6500206 2.4kW Med Low Low Low Low Low Low Low Low
6HK(0,1)6500506 4.8kW Med Low Low Low Low Low Low Low Low
6HK(0,1)6500806 7.7kW Med Low Low Low Low Low Low
6HK(0,1)6501006
6HK36501025
9.6kW Med Low Low Low Low Low Low
6HK(1,2)6501306 12.5kW Med Low Med Low Low Low Low
6HK(1,2)6501506
6HK36501525
14.4kW Med Low Med Low Low Low Low
6HK(1,2)6501806
6HK36501825
17.3kW Low Med Low Low Low Low
6HK(1,2)6502006
6HK46502025
19.2kW Low Med Med Med
6HK(1,2)6502506
6HK46502525
24kW Med Med
1.
(0,1) - 0 = no service disconnect OR 1 = with service disconnect.
2.
(1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect & breaker
jumper bar.
3.
6HK3 = 3-Phase with terminal block connectors only, 6HK4 = 3-Phase with service disconnect.
Table 5. KW & MBH Conversions - For Total Power Input Requirement
For a power distribution voltage that is different than the provided nominal voltage, multiply the kW and MBH
data from the table by the conversion factor in the following table.
DISTRIBUTION POWER NOMINAL VOLTAGE CONVERSION FACTOR
208V 240V 0.75
220V 240V 0.84
230V 240V 0.92
(Ins)DX-Kit4e-rev1.inddC-21