PMGB0406B rev.1
25
Table 8. Electrical Data For Multi-source Power Supply: 208/230-1-60
Air Handler
Models
Heater
Models
Total
Heater
Amp@
240V
Min. Circuit Ampacity MOP
*
208V 230V 208V 230V
Circuit Circuit
1st
*
2nd 3rd 1st
*
2nd 3rd 1st
*
2nd 3rd 1st
*
2nd 3rd
30B 6HK16501306 52 21.7 37.6 – 23.6 41.5 – 25 40 – 25 45 –
6HK16501506 60 24.5 43.3 – 26.8 47.9 – 25 45 – 30 50 –
36B
6HK16501306 52 22.0 37.6 – 24.0 41.5 – 25 40 – 25 45 –
6HK16501506 60 24.9 43.3 – 27.2 47.9 – 25 45 – 30 50 –
6HK16501806 72 42.3 39.0 – 46.4 43.1 – 45 40 – 50 45 –
6HK16502006 80 46.6 43.3 – 51.2 47.9 – 50 45 – 60 50 –
36C
6HK16501306 52 21.5 37.6 – 23.5 41.5 – 25 40 – 25 45 –
6HK16501506 60 24.4 43.3 – 26.7 47.9 – 25 45 – 30 50 –
6HK16501806 72 41.8 39.0 – 45.9 43.1 – 45 40 – 50 45 –
48C
6HK16501306 52 22.4 37.6 – 24.4 41.5 – 25 40 – 25 45 –
6HK16501506 60 25.3 43.3 – 27.6 47.9 – 30 45 – 30 50 –
6HK16501806 72 42.6 39.0 – 46.8 43.1 – 45 40 – 50 45 –
6HK16502006 80 47.0 43.3 – 51.5 47.9 – 50 45 – 60 50 –
48D
6HK16501306 52 22.4 37.6 – 24.4 41.5 – 25 40 – 25 45 –
6HK16501506 60 25.3 43.3 – 27.6 47.9 – 30 45 – 30 50 –
6HK16501806 72 42.6 39.0 – 46.8 43.1 – 45 40 – 50 45 –
6HK16502006 80 47.0 43.3 – 51.5 47.9 – 50 45 – 60 50 –
6HK16502506 100 47.0 43.3 21.7 51.5 59.9 24.0 50 45 25 60 60 25
60C
6HK16501306 52 23.9 37.6 – 25.9 41.5 – 25 40 – 30 45 –
6HK16501506 60 26.8 43.3 – 29.1 47.9 – 30 45 – 30 50 –
6HK16501806 72 44.1 39.0 – 48.3 43.1 – 45 40 – 50 45 –
60D
6HK16501306 52 23.9 37.6 – 25.9 41.5 – 25 40 – 30 45 –
6HK16501506 60 26.8 43.3 – 29.1 47.9 – 30 45 – 30 50 –
6HK16501806 72 44.1 39.0 – 48.3 43.1 – 45 40 – 50 45 –
6HK16502006 80 48.5 43.3 – 53.0 47.9 – 50 45 – 60 50 –
6HK16502506 100 48.5 43.3 21.7 53.0 59.9 24.0 50 45 25 60 60 25
*
MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
The 1st circuit includes blower motor
amps. Refer to your local codes to determine the correct wire size.