PMGB0406B rev.1
26
Air Handler
Models
Heater Models
1
Heater
Amps
@240V
Field Wiring
Min. Circuit Ampacity MOP
2
208V 230V 208V 230V
30B
6HK36501025 23.1 27.9 30.5 30 35
6HK36501525 34.6 40.4 44.3 45 45
36B
6HK36501025 23.1 28.3 30.9 30 35
6HK36501525 34.6 40.8 44.7 45 45
6HK36501825 41.6 48.4 53.2 50 55
6HK46502025
*
46.2 53.3 58.5 55 60
36C
6HK36501025 23.1 27.8 30.4 30 35
6HK36501525 34.6 40.3 44.2 45 45
6HK36501825 41.6 47.9 52.7 50 55
48C
6HK36501025 23.1 28.6 31.3 30 35
6HK36501525 34.6 41.1 45.1 45 50
6HK36501825 41.6 48.8 53.6 50 55
6HK46502025
*
46.2 53.6 58.9 55 60
48D
6HK36501025 23.1 28.6 31.3 30 35
6HK36501525 34.6 41.1 45.1 45 50
6HK36501825 41.6 48.8 53.6 50 55
6HK46502025
*
46.2 53.6 58.9 55 60
6HK46502525
*
57.7 66.2 72.7 70 80
60C
6HK36501025 23.1 30.1 32.8 35 35
6HK36501525 34.6 42.6 46.6 45 50
6HK36501825 41.6 50.3 55.1 55 60
60D
6HK36501025 23.1 30.1 32.8 35 35
6HK36501525 34.6 42.6 46.6 45 50
6HK36501825 41.6 50.3 55.1 55 60
6HK46502025
*
46.2 55.1 60.4 60 70
6HK46502525
*
57.7 67.7 74.2 70 80
1.
Asterisk (*) denotes the 20kW and 25kW heater models (6HK46502025 and 6HK46502525) come with
service disconnects standard. Single source power MCA and MOP requirements are given here only for
reference if used with ¿ eld installed single point power modi¿ cation (S1-32436041000).
2.
MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
The 1st circuit includes blower motor amps. Refer to your local codes to determine the correct wire size.
Table 9. Electrical Data for Single Source Power Supply: 208/230-1-60
(Ins)DX-Kit4e-rev1.inddC-26
(Ins)DX-Kit4e-rev1.inddC-26
2016/11/2515:32:46