PMGB0406B rev.1
39
Ɣ Ensure the installation distance between this DX-Kit and the air handler is the shortest possible.
Ɣ For the piping length, keep a maximum distance of 16.4ft (5 m) between the air handler and the
expansion valve box. Be certain the elevation difference between the air handler and the expansion
valve box DOES NOT exceed 6.6 ft (2 m).
Ɣ Be sure that the installation distance between the control box and the air handler is short enough
so that thermistor sensing is not distorted.
Ɣ Never install the thermistor cable in the same ducting as the power or control wirings.
Avoid unpackaging the DX-Kit until it arrives at the installation site.
Install the DX-Kit as soon as possible after unpacking.
Unpack and place the DX-Kit on the À oor. Position the DX-Kit with the bottom surface facing downward
on the soft packing insulation material. Any super¿ cial damage to this item can compromise its moisture
sealing qualities.
Do not lay any objects on this product.
This DX-Kit is compatible with the following air handler models.
DX-Kit Model Air Handler Model
EXV-018E AP18BX21
EXV-024E AP24BX21
EXV-030E AP30BX21
EXV-036E AP36BX21, AP36CX21
EXV-048E AP48DX21, AP48CX21
EXV-060E AP60DX21, AP60CX21
17.2 Applicable Model