Merging Data Between Sites Enterprise Configuration
3-16 24-10515-21 Rev. –
This document contains confidential and proprietary information of Johnson Controls, Inc.
© 2010 Johnson Controls, Inc.
12. For FDA-compliant systems, re-establish FDA signatures:
From the P2000 main menu select System>Database Maintenance.
Enter the password when prompted and click OK.
From the database maintenance window, select Calculate Digital
Signature and click the Perform button.
Click OK to confirm the action.
In the Calculate Digital Signature window, click the Select All button and
then the Perform button.
P2000 will now perform the operations on the database. This may take a
few minutes. When the process is completed make sure there are no
invalid signatures. Click Cancel to close the window.