Enterprise Configuration Configuring P2000 Regional Server
24-10515-21 Rev. – 4-13
This document contains confidential and proprietary information of Johnson Controls, Inc.
© 2010 Johnson Controls, Inc.
The recommended settings are:
Table 4-1: Recommended Replication Schedule
Publication Recommended Replication
Enterprise, Configuration,
Ba
dgeImages
Every 5 minutes
FDA, Alarms, Audit,
Ba
dgeImages FDA,
XAction
Every 1 hour (
for instant availability in Alarm
Monitors, use Remote Message Service
rather than more frequent replication).
13. View the new schedule settings and click Next.
14. Verify that Immediately is selected from the Initialize When drop-down list
and click Next.