UNDERWRITERS LABORATORIES® COMPLIANCE VERIFICATION SHEET
P2000 or P2K SYSTEM
Page 1 of 3
This product is listed under Underwriters Laboratories UL™ 1076 for Proprietary Burglar Alarm Units and Systems.
When installed at the site the following requirements must be met to comply with this standard.
1. Transient protection devices t
hat are installed must not be removed or defeated.
2. The computers audible alarm indi
cator must not be disabled.
3. All system components must be connected to a UL Li
sted Uninterruptible Power Supply that provides a
minimum of 24 hours of AC emergency power.
4. The maximum number of Panels that may be connected to the P2000 or P2K system is 1000.
5. The P2000 or P2K shall give priority to signals in the order given below and shall annunciate subsequent
si
gnals at a rate no less than one every 10 seconds
Priority 0 Highest Priority Hold-up or Panic Alarm
Priority 1 Second Highest Burglar Alarm
Priority 2 Third Highest Burglar Alarm Supervision
Priority 3 Fourth Highest Other Supervisory Alarms
Priority 4 Fifth Highest Guard Tour
6. The “Pop-up” feature for input points must be enabled.
7. At the host computer (Central Station
), alarms must not be filtered away from the host using the feature
“Message Filtering”.
8. Alarms must not be forwarded away from the host compu
ter (Central Station) using the feature “Message
Forwarding”.
9. The “Panel Poll Interval” mu
st not exceed 90 seconds.
10. The “Host Poll Delay” must not exceed 200 seconds.
11. P2000 or P2K server must use trans
ient suppression devices on the LAN interfaces at the computers. The
table below specifies the devices that must be used for the various types of LAN interfaces.
LAN Interface Manufacturer of Device Device Part Number
10Base-2 Black Box® SP350A-R2 (In-line connector)
10Base-2 Black Box SP501A (“T” connector)
10Base-5 (AUI) Black Box SP362
10/100Base-T Black Box SP512A-R3
12. Systems requiring the use of a network hub, router, and/or serial port server shall have that equipment
inst
alled in a temperature controlled environment. The temperature controlled environment must be
maintained between 13 - 35C (55 - 95F) by the HVAC system. Twenty-four hour standby power shall be
provided for the HVAC system.
13. The installer shall incorporate a supp
ly line transient suppression device complying with the Standard for
Transient Voltage Surge Suppressors, UL 1449, with a maximum rating of 330 V. Supply line transient
suppression device is to be used with the power supply to the network hub, router, serial port server, serial-
to-ethernet converter and RS232-to-RS485 converter.
14. The 240 Vac configurations have not been tested by Underwriters Laboratories.
15. The workstation defined as “Server” must have t
he alarm monitor parameter set to “always active”.