CKM-CE75-E1M Installation and Wiring
24-10707-112 Rev. D
3-8
Mounting Procedures
This section includes two mounting procedures: one for the MR 50, and one for
the EP1501 and the MR51E (which mount the same way).
To mount an MR50:
1. Identify the mounting location in the enclosure.
An MR50 can only be mounted in location B, as shown in
Figure 3-7.
Figure 3-7: Mount Location for MR50
2. Select four plastic standoffs from the enclosure’s parts kit.
3. Visually identify the four integrated screws that correspond to the
holes in the MR50 board. These are different screws than those used
to mount an EP1501 or MR51E.
4. Screw the standoffs onto those integrated screws until tight.
5. Select four #6 screws from the enclosure’s parts kit.
6. Orient the MR50 board over the standoffs.
7. Screw one of the four #6 screws into the corresponding standoff until
tight. Repeat for the other three screws.
8. Once the board is mounted, refer to the manual for the board for
wiring instructions.