EasyManua.ls Logo

Johnson Controls Sabroe SAB 233 S - Minimum Compressor Flow at 3550 Rpm

Johnson Controls Sabroe SAB 233 S
171 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Engineering manual - SAB 193-233-283 S A-frame (including ATEX)
90/168
008831 en 2020.10
Technical data
6.4 Minimum compressor flow at 3550 rpm
The minimum flow capacity for each compressor varies depending on its geometry and its operat-
ing conditions. Typical minimum flow for each of our compressor models is listed below. Table 22
represents minimum suction flow with the slide valve fully unloaded.
Unit
Minimum flow*
CFM
m
3
/h
SAB 193 S
71
121
SAB 193 L 95 161
SAB 233 S 125 212
SAB 233 L 157 267
SAB 233 E 365 621
SAB 283 S 224 380
SAB 283 L 282 479
SAB 283 E 650 1104
SAB 283 X 478 812
Table 22: Minimum suction flow
* at 3550 rpm