Technical Specifications
Table 5: Accessories (Order Separately)
Code Number Description
SEN-600-1 Remote Inside Air Temperature Sensor
TE-6361M-1
1
Duct Mount Air Temperature Sensor
TE-636S-1
1
Strap-Mount Temperature Sensor
TEC-6H-PIR
2
Cover with Occupancy Sensor
1. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the
TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details.
2. The TEC-6H-PIR Accessory Cover can be used to replace the existing cover on a non-PIR T60xDFH-4 Series Thermostat
Controller to provide occupancy sensing capability.
Table 6: Display Messages
Display Function
Service Indicates that there is a service alarm in accordance with the programmable Binary Input (BI2).
Filter Indicates that the filter(s) is dirty in accordance with the programmable Binary Input (BI2).
Window Indicates that an outside window or door is open and has cancelled the thermostat controller heating
or cooling action in accordance with the programmable Binary Input (BI1).
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and
Occupancy Sensing Capability (Part 1 of 2)
Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or
Safety Extra-Low Voltage (SELV)
Relay/Triac
Contact
Rating
On/Off and
Floating
Control
30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A Inrush, Class 2 or SELV
Analog
Output Rating
Proportional
Control
0 to 10 VDC into 2k ohm Resistance (Minimum)
Fan Relay Output Rating 19 to 30 VAC, 1.0 A Maximum, 3.0 A Inrush
Auxiliary
Output Rating
Triac Output 19 to 30 VAC, 1.0 A Maximum, 3.0 A Inrush
Digital Inputs Voltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3
Analog Inputs Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative
Temperature Coefficient (NTC) Thermistor Sensors
Temperature Sensor Type Local 10k ohm Johnson Controls Type II NTC Thermistor Sensor
Wire Size 18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter) Recommended
Temperature
Range
Backlit Display -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments
Heating Control 40.0°F/4.5°C to 90.0°F/32.0°C
Cooling
Control
54.0°F/12.0°C to 100.0°F/38.0°C
Accuracy Temperature ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
Humidity ±5% RH from 20 to 80% RH at 50 to 90°F (10 to 32°C)
Minimum Deadband 2F°/1C° between Heating and Cooling
Ambient
Conditions
Operating 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing