Advanced Setup
Select fan coil system
type:
2 = 2-pipe fan coil
4 = 4-pipe fan coil
4
2
Step #4 only appears if step #3 = 2.
2-PIPE SYSTEM OPERATION
1= Heat only system
2= Cool only system
3= Heat/Cool Auto
changeover
4= Heat/Cool Aux Electric
heat, Lockout Electric Heat
when Hot Water is available
5= Heat/Cool total electric
heat, no Hot Water, only
Electric Heat.
Note: #3 & #4 require accessory
changeover sensor
4
3
Setup
Press
MODE
Press
MODE
Continued
I
4
Setup
Page 11
On
Off
See Page 20, Note #2
Select operation when
fan is in the Auto mode:
On = continuous low
speed fan
Off = only energize
during a heating or
cooling cycle.
5
AUTO
Press
MODE