T7200
P/N 24-85784-00186 Rev. A_Issue Date: 09 2018
English
PARAMETER SETTING (PART 2/2)
Code
T7200-
TB21-...JS0
T7200-
TF20-...JS0 Parameter Name Defaulf Function
15
Default display 00
00: Display room temp.
01: Display setpoint only
16
3
3
Auto changeover 00
00: Disable
01: Enable
17
Digital input function 00
00: Setpoint reduction when contact is Closed (UnOccupied)
01: Setpoint reduction when contact is Open (UnOccupied)
02: Dew Point Alarm when contact is Closed
03: Dew Point Alarm when contact is Open
04: Shut off Fan and Valves when contact is Closed
05: Filter Alarm when contact is Closed
06: Filter Alarm when contact is Open
18
Unit selection 00
00: Celsius degree (°C)
01: Fahrenheit degree (°F)
19
Temperature offset 0 Setting range -5 to 5°C (-9 to 9°F)
20
1
1
Fan speed 00
00: 3 Speed
01: 2 Speed (MED, LOW)
02: 1 Speed (LOW)
03: No Fan
21
Language 00
00: Chinese
01: English
22
Mode selection 00
00: Cooling/heating/ventilation
01: Cooling only
02: Heating
23
Back light 30 The back light will be OFF in 05 to 60 sec.
28
4
--- Sample time 10 Setting range 1 to 99
29
Deadband 1 Setting range 0 to 10°C (32 to 50°F)
30
4
--- KP 10 Setting range 1 to 99
31
4
--- KI 01 Setting range 0 to 99
32
5
5
TiO2/ESP operation 00
00: Operate separately (Pressing Timer button shortly)
01: Work in parallel with FCU fan
33
6
6
Inter stage difference 3 Setting range 0 to 10°C (32 to 50°F)
34
6
6
Heating stage 00
00: 2 Stages
01: 1 Stage
35
7
--- Set Damper Opening time control 00
00: Disable
01: Enable
36
7
---
Damper opening time, 75 - 174 seconds
(only AHU application)
00
00 - 99
(00 = 75 s / 99 = 174 s)
Note
Terminal blocks changes depending on the application selected, please check the table beside rst
The relay output are line voltage, they are connected with Terminal “L” internally
The digital input “OCC” can assume different meaning depending on parameter 17 setting
1 Appeared when application parameter is 00,01,02,03,04,05,07
2 Appeared when application parameter is 00,01,02,03,04,05
3 Appeared when application parameter is 01
4 Appeared when application parameter is 06 07
5 Appeared when application parameter is 03
6 Appeared when application parameter is 04
7 Appeared when application parameter is 06
ALARM CODE DESCRIPTION
Item Code Description
1 E1 Internal sensor warning.
2 HI High temperature warning. Room Temperature >55°C (>131°F)
3 LO Low temperature warning. Room Temperature <0°C (<32°F) or internal sensor opened.
4 E5 Dew point risk warning. Valves and fan are shut off when error is active.
icon is visible when TiO2/ESP command is active
icon ash when lter alarm is active

Other manuals for Johnson Controls T7200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls T7200 and is the answer not in the manual?

Johnson Controls T7200 Specifications

General IconGeneral
BrandJohnson Controls
ModelT7200
CategoryThermostat
LanguageEnglish

Related product manuals