PARAMETER SETTING
Press
and
button for 5 seconds at power o󰀨 mode to get in parameter list. Press to scroll forward and M button to scroll backward in
the list and use
and
button to change the parameter value.
Code
T9200-
TB21-1JS0
T9200-
TF20-1JS0 Parameter name Default Function
04
MUTE 00
Enable/disable the beep when push touch button:
00: Disable
01: Enable
05
OFFSET 0°C/0°F
Offset to be compensate the room temperature:
Step: 0.5°C (1°F)
Range: -5~5°C (-9-9°F)
06
UNOCC-CLG-SP
26°C/
79°F
Cooling setpoint unoccupied mode.
Not available for Boiler application
Step: 0.5°C (1°F)
Range: 22~32°C (72-90°F)
07
UNOCC-HTG-SP
18°C/
64°F
Heating setpoint unoccupied mode.
Step: 0.5°C (1°F)
Range: 10~21°C (50-70°F)
08
SMPL-TM 10 s
Sample time,
PID parameter, only for PID
Range: 1~99 s
09
PB 5
Proportion band,
PID parameter, only for PID
Range: 1~10
10
KI 10
Integration parameter,
PID parameter, only for PID
Range: 0~99
11
BL-TIMER 30
Backlight timer
Range: 5~99S
12
PWR-F-RSTT 02
Restart after power failure:
00: OFF
01: ON
02: Recovery
13
TIO2ESP-CTL 00
TIO2ESP control:
00: Automatic
01: Manual
For TIO2ESP application
16
KEY-LOCK 00
Key lock function:
00: No lockout
01: Level 1 >Lock all keys
02: Level 2 >Lock the keys except Fan Speed and Temp Adjustment keys
03: Level 3 >Lock the ON/OFF and Clock keys
04: Level 4 >Lock the keys except ON/OFF key
17
TEMP-DISP 00
UI display room temperature or set point:
00: Room Temperature
01: Setpoint
18
UNIT 00
Unit selection:
00: IP
01: SI
20
SF-VERSION Software version, read only