EasyManua.ls Logo

Johnson Controls T9200 - Parameter Setting (Part 2;2); Alarm Code Description

Johnson Controls T9200
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
T9200
P/N 24-11446-00018 Rev. B Issue Date: 11 2020
English
PARAMETER SETTING (PART 2/2)
Code
T9200-
TB21-1JS0
T9200-
TF20-1JS0 Parameter name Default Function
17
HTG-STG 02
00: One Heating Stage - Fan Coil
01: One Heating Stage - Floor Heating
02: Two heating stage
18
BI-PLRT 01
BI polarity:
00: Normally Close
01: Normally Open
19
OCC-OVRD 00
Override the OCC-S value:
00: No Override
01: Occupied
02: Unoccupied
21
FAN-DELAY 00 Fan off delay after valve closed, in seconds (0-99 s)
22
ECM-RLY 00
00: Disable
01: Enable
Note
Terminal blocks changes depending on the application selected, please check the table beside rst
The relay output are line voltage, they are connected with Terminal “L” internally
The digital input “OCC” can assume di󰀨erent meaning depending on parameter 12 setting
ALARM CODE DESCRIPTION
Item Code Description
1 E1 Internal sensor warning.
2 HI High temperature warning. Room temperature >55°C (>131°F)
3 LO Low temperature warning. Room temperature <0°C (<32°F) or internal sensor opened.
4 E5 Dew point risk warning. Valves and fan are shut off when error is active.
8 E6 Filter alarm
9 E7 BI warning

Related product manuals