Transmission range (for wireless
models)
50 ft (15.2 m) recommended indoor
250 ft (76.2 m) line of sight, maximum
Temperature
range
Backlit display -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° increments
Heating control 40.0°F/4.5°C to 90.0°F/32.0°C
Cooling control 54.0°F/12.0°C to 100.0°F/38.0°C
Accuracy Temperature ±0.9F°/±0.5C° at 70.0°F/21.0°C typical calibrated
Humidity ±5% RH from 20 to 80% RH at 50 to 90°F (10 to 32°C)
Minimum deadband 2F°/1C° between heating and cooling
Occupancy sensor motion
detection (occupancy sensing
models)
Minimum of 94 angular degrees up to a distance of 15 ft (4.6 m);
based on a clear line of sight
ambient
conditions
Operating 32°F to 122°F (0°C to 50°C); 95% RH maximum, noncondensing
Storage -4°F to 122°F (-20°C to 50°C); 95% RH maximum, noncondensing
Compliance BACnet
International
BACnet Testing Laboratories™ (BTL) 135-2001 Listed BACnet Advanced Application
Controller (B-AAC)
United States UL Listed, File E27734, CCN XAPX, Under UL60730
Networked models: FCC Compliant to CFR 47, Part 15, Subpart B, Class B
Wireless models: Transmission complies with FCC Part 15.247 regulations for low
power unlicensed transmitters; transmitter identification FCC: OEJ-WRZRADIO
Canada UL Listed, File E27734, CCN XAPX7, Under E60730
Networked models: Industry Canada, ICES-003
Wireless models: Industry Canada (IC) RSS-210;
Transmitter identification ZFR1810-1: IC: 279A-WRZRADIO
Europe (for
networked
models only)
CE Mark – Johnson Controls declares that this product is in compliance
with the essential requirements and other relevant provisions of the EMC Directive
and the RoHS Directive.
Australia and
New Zealand
RCM Mark, Australia/NZ Emissions Compliant
shipping
weight
Models without
occupancy
sensor
0.75 lb (0.34 kg)
Models with
occupancy
sensor
0.77 lb (0.35 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or
misuse of its products.
Software terms
Use of the software that is in (or constitutes) this product or access to the cloud or hosted services applicable
to this product, if any, is subject to applicable terms set forth at www.johnsoncontrols.com/techterms
. Your
use of this product constitutes an agreement to such terms. If you do not agree to be bound by such terms, you
may return the unused product to your place of purchase.
TEC3000 Series Networked And Wireless Proportional Fan Coil And Individual Zone Thermostat
Controllers With Dehumidification Capability (Part 2 of 2 )