EasyManua.ls Logo

Johnson Controls TEC3030-14 - User Manual

Johnson Controls TEC3030-14
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
TEC3000 Series Proportional Fan Coil
Thermostats Installation Guide
Applications
The networked TEC3000 Series Thermostat Controllers
are stand-alone and field-selectable BACnet
®
MS/TP or
N2 networked devices. Wireless networked models of the
TEC3000 Series Thermostat Controller are also available.
Proportional Fan Coil and Individual Zone Thermostat
Controllers provide control of the following:
Local hydronic reheat valves
Pressure-dependent variable air volume (VAV)
equipment with or without local reheat
Two- or four-pipe fan coils
Cabinet unit heaters
Other individual zone equipment using an on/off or
floating control input
The networked models feature a field-selectable
Building Automation System (BAS) BACnet MS/TP or N2
communication capability that enables remote monitoring
and programming for efficient space temperature control.
The wireless models (TEC30xx-xx-000) are compatible
only with the WNC1800/ZFR182x Pro Series Wireless Field
Bus System that enables communication with a building
automation system (BAS). The new wireless models
(TEC31xx-14-000) are compatible only with WRG1830/
ZFR183x Pro Series Wireless Field Bus System. All models
include a USB port configuration that reduces installation
time to allow simple backup and restore features from a
USB drive, which enables rapid cloning of configuration
between similar units.
Some models have occupancy sensing capability built into
the device. These thermostat controllers maximize up to
30% energy savings in high-energy usage commercial
buildings, such as schools and hotels, during occupied
times by using additional standby setpoints.
All models feature an intuitive onboard touchscreen UI
with backlit display that makes setup and operation quick
and easy. For Single-or Two-Stage Economizer Thermostat
Controller models, only the single-speed fan configuration
is supported. For TEC3x1x and TEC3x2x models, multiple
fan configurations are supported for fan coil equipment
types, as follows:
Single-speed
Multi-speed (two or three discrete speeds)
Variable-speed/EC motors (0 to 10 VDC control)
Some models support dehumidification on two-pipe
fan coil units with reheat, and four-pipe fan coil units
with or without reheat. When no heating is required,
the thermostat controller monitors space humidity and
activates dehumidification control as necessary. Heat
and/or reheat is used as required to maintain the space
temperature. For optimal dehumidification performance,
use a fan coil unit that has a multi-speed or variable-speed
fan (VSF).
Important: The TEC3000 Series Thermostat
Controller is intended to provide an input to
equipment under normal operating conditions.
Where failure or malfunction of the thermostat
controller could lead to personal injury or property
damage to the controlled equipment or other
property, additional precautions must be designed
into the control system. Incorporate and maintain
other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of
or protect against failure or malfunction of the
thermostat controller.
Important: Le TEC3000 Series Thermostat Controller
est destiné à transmettre des données entrantes
à un équipement dans des conditions normales
de fonctionnement. Lorsqu'une défaillance ou un
dysfonctionnement du thermostat controller risque
de provoquer des blessures ou d'endommager
l'équipement contrôlé ou un autre équipement, la
conception du système de contrôle doit intégrer des
dispositifs de protection supplémentaires.Veiller
dans ce cas à intégrer de façon permanente d'autres
dispositifs, tels que des systèmes de supervision
ou d'alarme, ou des dispositifs de sécurité ou de
limitation, ayant une fonction d'avertissement
ou de protection en cas de défaillance ou de
dysfonctionnement du thermostat controller.
North American emissions
compliance
United States
This equipment has been tested and found to comply with
the limits for a Class B digital device, pursuant to Part 15
of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in
a residential installation. This equipment generates,
uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions,
may cause harmful interference to radio communications.
However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception,
which can be determined by turning the equipment
off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and
receiver.
Connect the equipment into an outlet on a circuit
different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV
technician for help.
LIT-12013162
2020-12-15
TEC3322-1x-xxx, TEC3323-1x-xxx, TEC3622-1x-xxx,
TEC3623-1x-xxx, TEC3022-1x-xxx, TEC3023-1x-xxx,
TEC312x-14-xxx

Questions and Answers

  • X
    xsimpsonSep 16, 2025
    Why does Johnson Controls TEC3030-14 Thermostat provide an error when trying to upgrade firmware?
    • L
      Linda HancockSep 16, 2025
      If your Johnson Controls Thermostat provides an error when trying to upgrade firmware, it means that the firmware on the USB drive is below the minimum required version (Error code 1025). Use firmware version 3.0.2.xxxx (for networked models) or 2.0.2.xxxx (for wireless models) or higher. A reboot is required to clear the Firmware Mismatch fault that occurs.
  • M
    Michael RamirezSep 17, 2025
    Why TEC3000 zone temperature doesn't change fast enough?
    • P
      Patrick LynchSep 17, 2025
      If the TEC3000 zone temperature does not change fast enough compared to the measured zone temperature from a verification device, it is because the TEC3000 is configured by default for larger spaces with normal-sized equipment when a proportional device is active. To resolve this, select Control Setup > Tuning > Equipment Size > Oversized.
  • F
    Frank ShafferSep 18, 2025
    Why zone space temperature increases/decreases too much in unoccupied mode on Johnson Controls TEC3030-14 Thermostat?
    • H
      holtjamieSep 18, 2025
      If the zone space temperature increases or decreases too much when the unit is active in unoccupied mode on your Johnson Controls Thermostat, it means that the heating and cooling equipment are too big for the unoccupied space. Decrease the Unoccupied Off Delay parameter from 10 minutes to a more appropriate time for the equipment configuration.
  • T
    Terri MuellerSep 18, 2025
    Why does Johnson Controls TEC3030-14 Thermostat provide an error when trying to back up settings?
    • O
      owoodsSep 18, 2025
      If your Johnson Controls Thermostat provides an error when trying to back up settings, it means the USB drive is defective. Try a different USB drive.
  • J
    John HillSep 23, 2025
    Why does Johnson Controls Thermostat provide an error when trying to restore settings from a backup?
    • D
      Dennis DunnSep 23, 2025
      If your Johnson Controls Thermostat provides an error when trying to restore settings from a backup, it could be due to several reasons. The USB drive might be defective, so try a different USB drive. The Restore file might be corrupt, so try restoring a different backup file. The Restore file might be from an incompatible model TEC, so ensure that the backup file being restored was from the same model TEC.
  • J
    justin40Sep 23, 2025
    Why Johnson Controls Thermostat is unable to access a USB drive?
    • S
      Stephanie HoganSep 23, 2025
      If your Johnson Controls Thermostat is unable to access a USB drive, it could be because the drive is formatted as NTFS or another unsupported format. The TEC supports file allocation table (FAT) (for networked models), FAT16 (for wireless models), and FAT32 (for all models) formats only. Try reformatting the USB drive, or try a different USB drive with a supported format. Also, the USB drive might be defective, so trying a different drive is a good step.
  • M
    Miss Jennifer NicholsSep 23, 2025
    What to do if Johnson Controls TEC3030-14 displays Firmware Mismatch?
    • N
      Nancy ConnerSep 23, 2025
      If your Johnson Controls Thermostat displays a Firmware Mismatch, it could be due to a previous upgrade that did not complete. In this case, upgrade the TEC3000 to the latest released version and then upgrade it to the current version again. Alternatively, the previous downgrade might not have completed because the previous version is no longer supported; in this case, reboot the TEC3000 to clear the fault.
  • M
    Michelle HammondAug 23, 2025
    What to do if the Johnson Controls Thermostat shows 'Remote Zone Temp Fail'?
    • R
      riveratravisAug 23, 2025
      If your Johnson Controls Thermostat displays 'Remote Zone Temp Fail', it indicates that the External Zone Temperature sensor is either disconnected or has failed. Here's what you should do: 1. Check the sensor's wiring to ensure it's properly connected. 2. If the sensor was intentionally disconnected, reset the sensors through the menu. 3. If the problem continues, you may need to order replacement units and return the faulty devices to Johnson Controls under the RMA program.
  • A
    Amanda ArellanoSep 6, 2025
    What to do if Johnson Controls TEC3030-14 displays Calibration Corrupt?
    • K
      kimberlysinghSep 6, 2025
      If your Johnson Controls Thermostat displays 'Calibration Corrupt', it means that factory calibration data is lost or not installed. To resolve this, order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • K
    Kenneth CastilloSep 5, 2025
    What causes USB Malfunction on Johnson Controls Thermostat?
    • M
      Michelle WestSep 5, 2025
      If your Johnson Controls Thermostat reports a USB Malfunction, it indicates that a USB drive has malfunctioned and drawn more than the maximum allowed current. You can try inserting and using the USB drive again, or try a new USB drive. If the problem persists, order replacement units and return the affected devices to Johnson Controls under the RMA program.

Summary

Applications

North American emissions compliance

FCC compliance information for North American installations.

Installation

Location considerations

Guidelines for optimal placement of the thermostat controller.

Installing the thermostat controller

Step-by-step instructions for mounting the thermostat controller.

Wiring

Risk of Electric Shock

Warning about disconnecting power before electrical connections.

Terminal identification

Wiring diagrams

Setup and Configuration

Customizing the home screen

Customizing screen themes, brightness, and displayed information.

Using the USB port

Loading firmware, restoring settings, and communication setup.

Configuring the thermostat controller

Settings for unit type, fan, control mode, and occupancy.

Temperature setpoints

Adjusting cooling and heating setpoints for different modes.

Configuring occupancy

Setting up schedules, sensors, and occupancy modes.

Troubleshooting

Fault list

Table listing common faults, probable causes, and solutions.

Troubleshooting details

Specific issues with USB, board mismatch, and firmware errors.

Technical specifications

Repair information

Johnson Controls TEC3030-14 Specifications

General IconGeneral
BrandJohnson Controls
ModelTEC3030-14
CategoryThermostat
LanguageEnglish

Related product manuals