EasyManua.ls Logo

Johnson Controls TEC3613-14 - User Manual

Johnson Controls TEC3613-14
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
TEC3000 Series Proportional Fan Coil
Thermostats Installation Guide
Applications
The networked TEC3000 Series Thermostat Controllers
are stand-alone and field-selectable BACnet
®
MS/TP or
N2 networked devices. Wireless networked models of the
TEC3000 Series Thermostat Controller are also available.
Proportional Fan Coil and Individual Zone Thermostat
Controllers provide control of the following:
Local hydronic reheat valves
Pressure-dependent variable air volume (VAV)
equipment with or without local reheat
Two- or four-pipe fan coils
Cabinet unit heaters
Other individual zone equipment using an on/off or
floating control input
The networked models feature a field-selectable
Building Automation System (BAS) BACnet MS/TP or N2
communication capability that enables remote monitoring
and programming for efficient space temperature control.
The wireless models (TEC30xx-xx-000) are compatible
only with the WNC1800/ZFR182x Pro Series Wireless Field
Bus System that enables communication with a building
automation system (BAS). The new wireless models
(TEC31xx-14-000) are compatible only with WRG1830/
ZFR183x Pro Series Wireless Field Bus System. All models
include a USB port configuration that reduces installation
time to allow simple backup and restore features from a
USB drive, which enables rapid cloning of configuration
between similar units.
Some models have occupancy sensing capability built into
the device. These thermostat controllers maximize up to
30% energy savings in high-energy usage commercial
buildings, such as schools and hotels, during occupied
times by using additional standby setpoints.
All models feature an intuitive onboard touchscreen UI
with backlit display that makes setup and operation quick
and easy. For Single-or Two-Stage Economizer Thermostat
Controller models, only the single-speed fan configuration
is supported. For TEC3x1x and TEC3x2x models, multiple
fan configurations are supported for fan coil equipment
types, as follows:
Single-speed
Multi-speed (two or three discrete speeds)
Variable-speed/EC motors (0 to 10 VDC control)
Some models support dehumidification on two-pipe
fan coil units with reheat, and four-pipe fan coil units
with or without reheat. When no heating is required,
the thermostat controller monitors space humidity and
activates dehumidification control as necessary. Heat
and/or reheat is used as required to maintain the space
temperature. For optimal dehumidification performance,
use a fan coil unit that has a multi-speed or variable-speed
fan (VSF).
Important: The TEC3000 Series Thermostat
Controller is intended to provide an input to
equipment under normal operating conditions.
Where failure or malfunction of the thermostat
controller could lead to personal injury or property
damage to the controlled equipment or other
property, additional precautions must be designed
into the control system. Incorporate and maintain
other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of
or protect against failure or malfunction of the
thermostat controller.
Important: Le TEC3000 Series Thermostat Controller
est destiné à transmettre des données entrantes
à un équipement dans des conditions normales
de fonctionnement. Lorsqu'une défaillance ou un
dysfonctionnement du thermostat controller risque
de provoquer des blessures ou d'endommager
l'équipement contrôlé ou un autre équipement, la
conception du système de contrôle doit intégrer des
dispositifs de protection supplémentaires.Veiller
dans ce cas à intégrer de façon permanente d'autres
dispositifs, tels que des systèmes de supervision
ou d'alarme, ou des dispositifs de sécurité ou de
limitation, ayant une fonction d'avertissement
ou de protection en cas de défaillance ou de
dysfonctionnement du thermostat controller.
North American emissions
compliance
United States
This equipment has been tested and found to comply with
the limits for a Class B digital device, pursuant to Part 15
of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in
a residential installation. This equipment generates,
uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions,
may cause harmful interference to radio communications.
However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception,
which can be determined by turning the equipment
off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and
receiver.
Connect the equipment into an outlet on a circuit
different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV
technician for help.
LIT-12013162
2020-12-15
TEC3322-1x-xxx, TEC3323-1x-xxx, TEC3622-1x-xxx,
TEC3623-1x-xxx, TEC3022-1x-xxx, TEC3023-1x-xxx,
TEC312x-14-xxx

Questions and Answers

  • A
    Angelica SmithSep 4, 2025
    How to fix Fan Lock on Johnson Controls TEC3613-14 Thermostat?
    • L
      Leah BautistaSep 4, 2025
      If your Johnson Controls Thermostat displays 'Fan Lock', it means the switch connected to the BI configured for Fan Lock did not sense airflow within 10 seconds of starting the fan, and control has been shut down. Here's how to address it: 1. Inspect equipment to ensure the fan functions. 2. Check sensor functionality with an ohmmeter and verify wiring to the TEC. 3. Reset the fault by entering the menu, selecting Fault Status, and selecting the Fan Lock. 4. If the problem persists, order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • S
    Susan BoyerSep 3, 2025
    How to solve Open Window alert on Johnson Controls TEC3613-14?
    • K
      Kelly RogersSep 3, 2025
      If your Johnson Controls Thermostat displays an 'Open Window' alert, it means the switch connected to the BI configured for Open Window senses that the window is opened, and control has shut down. To resolve this: 1. Close the window to resume control. 2. Check sensor functionality with an ohmmeter and verify the wiring to the TEC. 3. If the problem persists, order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • J
    Jimmy JonesSep 2, 2025
    Why Johnson Controls Thermostat shows Humidity Unreliable?
    • N
      Norman GarzaSep 2, 2025
      If your Johnson Controls Thermostat displays 'Humidity Unreliable', it means the zone humidity reading was reliable but has now failed. If the source of zone humidity was the onboard sensor, contact Johnson Controls product sales and support. If the source of zone humidity was a BAS, check the BAS to ensure it is still online and providing the TEC with the humidity reading. If removal of the BAS mapping was intentional, reset sensors through the menu.
  • R
    Ruben HarrisSep 1, 2025
    Why Johnson Controls Thermostat shows Zone Temp Unreliable?
    • J
      Jane CastilloSep 1, 2025
      If your Johnson Controls Thermostat indicates that the Zone Temp is Unreliable, it means all sources of zone temperature, including the onboard sensor, are unreliable. To resolve this, order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • M
    Michele RodriguezAug 31, 2025
    What does Changeover Fail mean on Johnson Controls TEC3613-14 Thermostat?
    • S
      smithsarahAug 31, 2025
      If you see a 'Changeover Fail' message on your Johnson Controls Thermostat, it means the Supply Temperature Sensor is not installed, has failed, or has been disconnected, and the TEC can no longer detect changeover mode to cool or heat. Follow the same steps as for a Supply Temp Fail alarm to resolve this issue.
  • D
    dawn51Aug 30, 2025
    What to do if Johnson Controls TEC3613-14 Thermostat displays Dehum Unavailable?
    • G
      Gabriel OdomAug 31, 2025
      If your Johnson Controls Thermostat displays 'Dehum Unavailable', it means that dehumidification is unavailable because the zone humidity sensor has failed or the humidity reading is not reliable. If the source of zone humidity was a BAS, check the BAS to ensure that it is still online and is providing the TEC with the humidity reading. If removal of the BAS mapping was intentional, reset the sensors through the menu. If the problem persists, order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • C
    charles35Aug 29, 2025
    What to do if Johnson Controls Thermostat displays Touchscreen Unavailable?
    • J
      Jamie WilliamsAug 30, 2025
      If your Johnson Controls Thermostat displays 'Touchscreen Unavailable', it indicates that the touchscreen components have failed to initialize. First, try rebooting the controller. If the problem persists, order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • S
    Sean SmithAug 28, 2025
    What to do if Johnson Controls Thermostat displays Controller Fault?
    • J
      Jason LambAug 29, 2025
      If the Johnson Controls Thermostat displays Controller Fault, this means that the controller has detected an internal fault that it cannot recover, or an unknown error has prevented the controller from turning on. In either case, order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • F
    fchavezAug 28, 2025
    What to do if Johnson Controls TEC3613-14 shows Internal Sensor Fail?
    • W
      William ShepherdAug 28, 2025
      If your Johnson Controls Thermostat displays an Internal Sensor Fail, it means that an internal sensor has failed on the TEC. The solution is to order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • R
    Ryan CastroAug 27, 2025
    How to fix Supply Temp Fail on Johnson Controls TEC3613-14?
    • A
      Amy BeanAug 27, 2025
      If your Johnson Controls Thermostat shows a Supply Temp Fail error, it indicates that the External Supply Temperature sensor has either been disconnected or has failed. To resolve this: 1. Check the wiring of the sensor. 2. If the disconnection was intentional, reset the fault by going to the menu, then Control Setup, and selecting Inputs to reset the sensors. 3. If the problem persists, order replacement units and return the affected devices to Johnson Controls under the RMA program.

Summary

Important Safety and Operational Guidance

North American Emissions Compliance

Installation Overview

Wiring Procedures

Wiring Safety and Best Practices

Emphasizes crucial safety warnings and regulatory compliance for electrical connections.

Terminal Identification

Wiring Diagrams

Setup and Adjustments Overview

Touchscreen Icons Reference

USB Port Operations

Loading Firmware

Step-by-step guide to update the thermostat's firmware via USB.

Backing Up and Restoring Settings

Instructions for saving and retrieving thermostat configurations using a USB drive.

Network Configuration

Fan Coil Supply Fan Configuration

Control and Fan Mode Settings

Changeover Configuration

Dehumidification Control Setup

Temperature Setpoint Configuration

Occupancy Configuration

Local Schedule Setup

Motion Sensor Configuration

PID;PRAC+ Control Tuning

Configurable Binary Inputs

Auxiliary Output Configuration

Commissioning Mode and Scheduled Circulation

Configurable Analog Inputs (AIs)

Networked Sensors

Sensor Data Priorities and Diagnostics

Available Fault Diagnostics

Lists and describes potential faults, including fan status, runtime, temperature alarms, and trends.

Troubleshooting Faults

Troubleshooting Details

Technical Specifications

Johnson Controls TEC3613-14 Specifications

General IconGeneral
ModelTEC3613-14
DisplayLCD
Power Supply24V AC
MountingWall Mount
ProgrammableYes
Backup BatteryNo
TypeDigital
ControlCooling and Heating
Stages1
CompatibilityHeat Pump

Related product manuals