1/3 TVI-TD-6007 Thermostat_1109
Subject to changes without prior notice
DESCRIPTION
TVI-TD-6007 series thermostat is mainly used in central air-conditioning and
heating system. It detects room temperature and compares it with setting point,
then provides control signal to central air-conditioning fan coil cool / heat motorized
valves or other actuating mechanism. It can also control the fan blower of fan coil
units and adjust the fan speed. When the TVI-TD-6007 thermostat is turned off or
get power supply after system power shut off, it can output a return signal to make
the motorized valves or other actuating mechanism return.
CHARACTERISTICS
Power surge and instant pulse protection.
Output signal overtime protection function, auto-return function when the
thermostat is turned off or get first power supply (TVI-TD-6007F)
Fixed setting temperature function
Large LCD with background light shows the control state, ambient
temperature, setting temperature and fan speed.
With system on-off switch and fan speed switch.
Inside or outside long-distance temperature sensitive element
(NTC thermistor)
With ABS fireproof plastic, compliance with UL-94 standard.
TECHNICAL DATA
NAME
TVI-TD-6007A/B (2-pipe sys.)
TVI-TD-6007C (4-pipe sys.)
TVI-TD-6007F TVI-TD-6007P
POWER SUPPLY 24Vac; 220/230Vac AC24V AC220V/230V
OUTPUT
24Vac, 1(0.8)A;
220/230Vac, 1(0.5)A
DC0-10V 10mA DC0-10V 5mA
POWER CONSUMPTION 0.6VA ; 6VA (without load)
0.6VA (without
load)
6VA
(without load)
FAN OUTPUT 24Vac, 2(1) A; 220/230Vac, 2(1)A 24Vac, 2(1) A
220/230Vac,
2(1)A
RETURN TIME ---
≥150s or 300s (for
option)
---
OVERTIME CUT OFF ---
Valve operate to the
same direction
≥150s (300s),
turns into overtime
protection state.
---
WORKING STATE On/off type Floating (PID) Modulating
CONTROL PRECISION ±0.5°C(±1°C)
CONTROL RANGE 10°C - 30°C or 50°F - 86°F
BACKGROUND LIGHT BlueB
SENSITIVE ELEMENT NTC thermistor 10KΩ (when at 25°C)
WORKING TEMPERATURE 0 ~ 55
o
C/32
o
F ~131
o
F
STORAGE TEMPERATURE -10 ~ 60°C/14
o
F ~140
o
F
AMBIENT HUMIDITY 90% RH maximum
TVI
-
TD
-
6007 Series
Thermostat
HVAC&R Parts and
Accessories™
by
Question and Answer IconNeed help?

Do you have a question about the Johnson Controls TVI-TD-6007 Series and is the answer not in the manual?

Johnson Controls TVI-TD-6007 Series Specifications

General IconGeneral
Power Supply24 VAC
DisplayLCD
Power SourceHardwired
Accuracy±1°F (±0.5°C)
MountingWall-mounted
ProgrammableYes

Summary

Product Overview and Specifications

Description

Provides control signal to central air-conditioning fan coil units, and controls fan speed.

Key Characteristics

Features include power surge protection, auto-return function, large LCD display, and NTC thermistor.

Technical Data

Details power supply, output, power consumption, fan output, return time, and operating parameters.

Operating Instructions and Wiring

Operating Instructions

Details cool/heat shift, fan control, temperature setting, and sensor configuration options.

Wiring Diagrams

Illustrates connections for different TVI-TD-6007 models including 2-pipe, 4-pipe, floating, and modulating.

Installation Guidelines

Installation Procedure

Instructions on removing the wiring terminal before wiring the thermostat.

Related product manuals