1.2.3 Measured and calculated pressure levels - recips.
Measuring Min. Max. Factory Note
Suction pressure
(bar)
High shutdown
High alarm
Low alarm
Low shutdown
-
1.5
-1.0
-1.0
-
9.0
6.0
6.0
-
5.0
2.5
1.5
-
3+4+5
3+4+5
3+4+5
Discharge pressure
(bar)
High shutdown
High alarm
Low alarm
Low shutdown
4.0
3.0
-
-1.0
24.0
22.0
-
-1.0
16.0
15.0
-
-1.0
1+6
1+6
-
1+5
Intermediate pressure (bar)
Two stage compressors only
High shutdown
High alarm
Low alarm
Low shutdown
4.0
3.0
-1.0
-1.0
24.0
22.0
10.0
10.0
7.0
6.0
-1.0
-1.0
1+6
1+6
1+6+16
1+6+16
Oil pressure (bar)
Calculated value
SMC100/TSMC/HPC
High shutdown
High alarm
Low alarm
Low shutdown
Low-low shutdown
5.0
5.0
0.5
0.5
0.0
7.0
7.0
5.0
5.0
1.5
6.0
5.5
4.0
3.5
0.5
2+5+16
2+5
2+5+14
2+5+14
2+5+32
Diff. pressure across oil filter
(bar)
Calculated value SMC100/
TSMC/HPC
High shutdown
High alarm
Low alarm
Low shutdown
0.0
0.0
-
-
10.0
7.0
-
-
6.0
4.0
-
-
2+11a
2+11a
-
-
Table 11: Measured and calculated pressure levels - reciprocating compressors
Operating Unisab III control
30/48
Operating manual - Unisab III
005650-en 2013.10

Other manuals for Johnson Controls Unisab III

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls Unisab III and is the answer not in the manual?

Johnson Controls Unisab III Specifications

General IconGeneral
BrandJohnson Controls
ModelUnisab III
CategoryControl Systems
LanguageEnglish

Related product manuals