1.2.2 Measured and calculated temperatures - screws
Measuring Min. Max. Factory Note
Discharge temperature (°C)
High shutdown
High alarm
Low alarm
Low shutdown
60.0
50.0
-65.0
-
130.0
120.0
-65.0
-
100.0
90.0
-65.0
-
1+6
1+6
-
-
Discharge temperature (°C)
SAB 157HR
High shutdown
High alarm
Low alarm
Low shutdown
60.0
50.0
-65.0
-
170.0
170.0
-65.0
-
120.0
110.0
-65.0
-
1+6
1+6
-
-
Oil temperature (°C)
All types except SAB 120-151,
SAB 157HR and SAB
193-233-283-355
High shutdown
High alarm
Low alarm
Low shutdown
40.0
30.0
10.0
0.0
80.0
70.0
50.0
40.0
65.0
60.0
45.0
40.0
2+7
2+7
2+7
2+7
Oil temperature (°C)
SAB 120-151, SAB 157HR and
SAB 193-233-283-355
High shutdown
High alarm
Low alarm
Low shutdown
40.0
30.0
10.0
0.0
110.0
110.0
50.0
40.0
75.0
70.0
45.0
40.0
2+7
2+7
2+7
2+7
Oil separator temperature
SAB 120-151, SAB 157HR,
SAB 193-233-283-355 and
SABflex
High shutdown
High alarm
Low alarm
Low shutdown
-
60.0
0.0
0.0
-
150.0
50.0
40.0
-
100.0
15.0
10.0
Process out temperature (°C)
High shutdown
High alarm
Low alarm
Low shutdown
-60.0
-60.0
-100.0
-100.0
100.0
100.0
100.0
100.0
60.0
50.0
4.0
2.0
1+6
1+6
1+6
1+6
Process in temperature (°C)
High shutdown
High alarm
Low alarm
Low shutdown
-60.0
-60.0
-100.0
-100.0
100.0
100.0
100.0
100.0
60.0
50.0
4.0
2.0
1+6
1+6
1+6
1+6
Suction gas superheat (°C)
Calculated value
High shutdown
High alarm
Low alarm
Low shutdown
6.0
5.5
0.0
0.0
120.0
120.0
40.0
40.0
110.0
100.0
2.0
0.0
2+7+12
2+7+12
2+7+10
2+7+10
Discharge gas superheat (°C)
Calculated value
Low alarm
Low shutdown
Set point 1
Set point 2
5.0
0.0
0.0
0.0
40.0
40.0
999.9
999.9
15.0
10.0
5.0
10.0
2+7+10
2+7+10
23
23
Table 9: Measured and calculated temperatures - screw compressors
Measuring Min. Max. Factory Note
User input 1
(4-20 mA)
High shutdown
High alarm
Low alarm
Low shutdown
-999.9
-999.9
-999.9
-999.9
999.9
999.9
999.9
999.9
0.0
0.0
0.0
0.0
3+18
3+18
3+18
3+18
Table 10: 4-20 m User input 1 signal
Operating Unisab III control
Operating manual - Unisab III
005650-en 2013.10
29/48

Other manuals for Johnson Controls Unisab III

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls Unisab III and is the answer not in the manual?

Johnson Controls Unisab III Specifications

General IconGeneral
BrandJohnson Controls
ModelUnisab III
CategoryControl Systems
LanguageEnglish

Related product manuals