1.5. Timers
1.5.1 Timer values - screw compressors
No. Value Factory Low High Unit
Adjust-
able
1 Start-start delay 1/2 1200 600/60 3600 Sec. Yes
2 Stop-start delay 300 60 3600 Sec. Yes
3 Start delay 300 0 3600 Sec. Yes
4 Stop delay 300 60 3600 Sec. Yes
5 Suction ramp 0 0 1200 Sec. Yes
6 Slide max. 300 60 3600 Sec. Yes
7 Prelub. 1/2/3/4/5/6
10/60/0/6/50/0
0 120 Sec. Yes
8 Oil flow 1/2/3/4/5/6
600/90/60/120/600/0
- -
Sec. No
9 Oil flow delay 1/2/3/4/5/6 50/0/20/10/0/50 - - Sec. No
10 No oil/flow 1/2/3/4/5/6 10/2/6/120/30/30 - - Sec. No
11 Lubrication time/flow 1/2 60/300 - - Sec. No
12 Differential pressure OK 60 - - Sec. No
13 Oil pressure low 1/2/3/4 45/300/45/15 - - Sec. No
14 Filter diff. pressure high 1/2 300/600 60 1200 Sec. Yes
15 Oil temperature low 300 - - Sec. No
16 Oil temperature high 300 - - Sec. No
17 Superheating low 300 - - Sec. No
18 Superheating high 300 - - Sec. No
19 Discharge pressure overload 300 - - Sec. No
20 Current overload 300 - - Sec. No
21 Motor start 45 5 120 Sec. Yes
22 PMS feedback 60 10 3600 Sec. Yes
23 F.F. Pump start 10 5 30 Sec. Yes
24 Oil pump start 10 5 30 Sec. Yes
25 Oil rectifier start 900 0 3600 Sec. Yes
26 Oil rectifier delay 300 0 3600 Sec. Yes
27 Oil rectifier disable 3600 0 7200 Sec. Yes
28 Start high pressure 30 0 120 Sec. Yes
29 No chiller 10 - - Sec. No
30 Capacity negative 5000 60 20000 Sec. Yes
31 Start unload 1/2/3 15 0 60 Sec. Yes
32 Low suction pressure 0 0 60 Sec. Yes
33 Lubricating pressure 1/2 120/180 - - Sec. No
34 Vi-pause 1/2 60/7 - - Sec. No
35 Oil log shutdown 30 0 300 Sec. Yes
36 Low oil flow 1/2 180/600 - - Sec. No
37 Oil circuit alarm 600 - - Sec. No
38 Oil circuit shutdown 900 - - Sec. No
39 SSSTV stop delay 40 20 60 Sec. Yes
40 Max. start-up time 600 60 24000 Sec. Yes
41 Oil return open 30 5 600 Sec. Yes
42 Oil return close 900 0 32400 Sec. Yes
43 By-pass start 30 5 600 Sec. Yes
44 Flow evaporator 5 2 15 Sec. Yes
45 Flow condenser 5 2 15 Sec. Yes
Operating Unisab III control
42/48
Operating manual - Unisab III
005650-en 2013.10

Other manuals for Johnson Controls Unisab III

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls Unisab III and is the answer not in the manual?

Johnson Controls Unisab III Specifications

General IconGeneral
BrandJohnson Controls
ModelUnisab III
CategoryControl Systems
LanguageEnglish

Related product manuals