Table 4: Technical specifications WRG
Specification Description
Transmission Power Wi-
Fi Access Point dongle
(maximum)
100mW
Transmission Range Wi-
Fi Access Point dongle
(typical)
WiFi communication:
30 m (100 ft) line-of-sight indoors
Transmission Power
ZFR183x Mesh (via
connected ZFR1831
Router)
User Selectable
100mW (default)
50mW
25mW
10mW
Transmission Range
ZFR1831 Mesh (via
connected ZFR1831
Router)
75 m (250 ft) Maximum at 100mW
304.8 m (1000 ft) Maximum Line-of-Sight
Note: Actual range is dependent on site and installation conditions.
Serial interfaces One ZFR Radio port (one 6-pin RJ12 jack and one 4-pin screw terminal)
One FC Bus port (one 4-pin screw terminal)[not used]
Three USB ports (one Micro-B port, and two USB A ports). All support USB 2.0 and Open
Host Controller Interface [Open HCI] specification.
Dimensions
(H x W x D)
190 mm x 125 mm x 44.5 mm (7.48 in. x 4.92 in. x 1.75 in.)
Housing White Polycarbonate and Acrylonitrile butadiene styrene (ABS) blend
Weight .387kg (.852 lbs)
Web browser
requirements for
computers and
handheld devices
Computer:
Windows Internet Explorer
®
10 and Windows Internet Explorer 11, or Google
®
Chrome
Handheld device:
The handheld device must run either Internet Explorer Mobile for Windows
®
Mobile version 5 or
version 6 operating system (OS); Android
or Google Chrome. Other web browsers may display
the UI, but the functionality is not guaranteed.
United States: UL Listed File E107041, CCN PAZX, UL 916, Energy Management Equipment, FCC
Compliant to CFR47, Part 15, Subpart B, Class A.
Compliance
Canada: UL listed file E107041, CCN PAZX7, CAN/CSA C22.2 No.205, Signal Equipment; Industry
Canada Compliant.
The performance specifications are nominal and conform to acceptable industry standard. For
application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson
Controls shall not be liable for damages resulting from misapplication or misuse of its products.
Appendix A: Reset Network Settings
About this task: The Reset Network Settings function resets Wi-Fi and Ethernet settings. Use this
function when you forget your connection credentials.
WARNING: There are two access holes on the front of the WRG1830, if you press the wrong
button you can permanently disable the WRG1830. The reset button is the button on the right
as shown in Figure 5
To reset the Wi-Fi and Ethernet settings, complete the following steps:
1. Press and hold the RESET button for two seconds. The FAULT LED flickers slowly.
2. Release the RESET button within three seconds. The FAULT LED continues to flicker slowly.
Wireless Router Gateway Installation Guide12