Items
LCL TEMP SET
CR BUFFER
LCL TEMP CE
LOW LELT
HIGH LCLT
LEP UNLOAD
LEP SHUT DOWN
HOLD LOAD D.P
UNLOAD D.P
HIGH D.P.SHUTDOWN
UNLOAD CURR.
DELTA T
LISV TEMP
Defult values
45.0
2.5
1.0
2.0
52.0
175KPa
165KPa
1286KPa
1303KPa
1356KPa
95%
4.5
80.0
Setting range
30.0~50.0
1.0~2.5
0.5~2.0
1.0~7.0
30.0~52.0
150.0~300.0 KPa
150.0~300.0 KPa
100.0~1400.0 KPa
100.0~1400.0 KPa
100.0~1400.0 KPa
10~98%
2.0~6.0
50.0~80.0
Access level
User password
User password
User password
Service password
Service password
Service password
Service password
Service password
Service password
Service password
Service password
Service password
Service password
(4) Assignable parameters setting and defult values (HP mode)
YEWS-E Water Cooling Screw Chiller/Heat Pump
Items
LCL TEMP SET
CR BUFFER
LCL TEMP CE
LOW LELT
HIGH LCLT
LEP UNLOAD
LEP SHUT DOWN
HOLD LOAD D.P
UNLOAD D.P
HIGH D.P.SHUTDOWN
UNLOAD CURR.
DELTA T
LISV TEMP
Defult values
55.0
2.5
1.0
2.0
62.0
175KPa
165KPa
1660KPa
1680KPa
1745KPa
95%
4.5
80.0
Setting range
30.0~60.0
1.0 2.5
0.5~2.0
1.0~7.0
30.0~62.0
150.0~300.0 KPa
150.0~300.0 KPa
100.0~1700.0 KPa
100.0~1700.0 Kpa
100.0~1800.0 KPa
10~98%
2.0~6.0
50.0~80.0
Access level
User password
User password
User password
Service password
Service password
Service password
Service password
Service password
Service password
Service password
Service password
Service password
Service password