OVERVIEW
This screen allows definition of the necessary commu-
nications parameters. Presently, there are no COM 2
communications features available.
DISPLAY ONLY
None
PROGRAMMABLE
Chiller ID
Access Level Required: OPERATOR
Define the numeric chiller ID when used within a BAS
network of chillers. This ID number is also printed at
the top of reports obtained with a local printer.
Printer Setup and COM 2 Setup
Access Level Required: OPERATOR
Pressing either key places a green selection box around
the first changeable parameter. Use the ▲ and ▼ keys
to place the selection box around the desired param-
eter to be changed. With the selection box around the
desired parameter, press the ENTER (ü) key. A dialog
box is displayed permitting data entry.
COMMS SCREEN
COMMS SCREENFIGURE 25 -
Printer Baud Rate
Define the baud rate at which the panel shall commu-
nicate to the printer.
Printer Data Bits
Define the number of data bits with which the panel
shall communicate to the printer.
Printer Parity Bits
Define the parity (NONE-ODD-EVEN) with which
the panel shall communicate to the printer.
Printer Stop Bits
Define the number of stop bits with which the panel
shall communicate to the printer.
COM 2 Baud Rate
Define the baud rate at which the panel shall communi-
cate through the modem port.
COM 2 Data Bits
Define the number of data bits at which the panel shall
communicate through the modem port.